5.10 GROUP 3.10: AUTOMATIC RESET
Table 64: Autoreset settings
Index Parameter Min Max Unit Default ID Description
P3.10.1 Automatic Reset 0 1 0 * 731
0 = Disabled
1 = Enabled
P3.10.2 Restart Function 0 1 1 719
0 = Flying start
1 = According to P3.2.4.
P3.10.3 Wait Time 0.10
10000.0
0
s 0.50 717
P3.10.4 Trial Time 0.00
10000.0
0
s 60.00 718
P3.10.5 Number of Trials 1 10 4 759
P3.10.6
Autoreset: Under-
voltage
0 1 1 720
0 = No
1 = Yes
P3.10.7
Autoreset: Overvolt-
age
0 1 1 721
0 = No
1 = Yes
P3.10.8
Autoreset: Overcur-
rent
0 1 1 722
0 = No
1 = Yes
P3.10.9 Autoreset: AI Low 0 1 1 723
0 = No
1 = Yes
P3.10.10
Autoreset: Unit Over-
temperature
0 1 1 724
0 = No
1 = Yes
P3.10.11
Autoreset: Motor
Overtemperature
0 1 1 725
0 = No
1 = Yes
P3.10.12
Autoreset: External
Fault
0 1 0 726
0 = No
1 = Yes
P3.10.13
Autoreset: Under-
load Fault
0 1 0 738
0 = No
1 = Yes
P3.10.14
Autoreset: PID
Supervision Fault
0 1 0 776
0 = No
1 = Yes
P3.10.15
Autoreset: Ext PID
Supervision Fault
0 1 0 777
0 = No
1 = Yes
* The selection of the application with parameter P1.2 Application gives the default value.
See the default values in 12.1 The default values of parameters in the different applications.