The sensor is put in position 1. The pressure in the pipe stays constant when there is no flow.
But with flow, the pressure decreases farther in the pipe. To compensate for this, lift the
setpoint as the flow increases. Then the output frequency makes an estimate of the flow, and
the setpoint increases linearly with the flow.
With flow and compensation
Position 1 Position 2
Pressure
No flow
Pipe length
Setpoint
Max Freq and FlowMin Freq and Flow
Setpoint + Max compensation
Setpoint
PTPT
Fig. 86: Enable setpoint 1 for pressure loss compensation
10.14.8 SOFT FILL
The Soft fill function is used to move the process to a set level at a slow speed before the PID
controller starts to control. If the process does not go to the set level during the timeout, a
fault shows.
You can use the function to fill an empty pipe slowly and prevent strong currents of water
that could break the pipe.
PARAMETER DESCRIPTIONS VACON · 313
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
10

Table of Contents

Other manuals for Vacon 100 flow

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 100 flow and is the answer not in the manual?

Vacon 100 flow Specifications

General IconGeneral
Protection classIP20
Communication interfaceRS-485
Operating temperature-10°C to +50°C
Storage temperature-40°C to +70°C
Ambient temperature-10°C to +40°C
Control methodSensorless vector control
Communication protocolsCANopen
ApprovalsCE, UL
I/O2 analog inputs
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature
Frequency range0 Hz to 400 Hz
Humidity5% to 95%, non-condensing
Voltage range208-240 V

Related product manuals