Table 115: The user level parameters
Index Parameter Min Max Unit Default ID Description
P8.1 User Level 1 3 1 1194
1 = Normal. All the
menus are visible in
the main menu.
2 = Monitoring. Only
the monitoring and
user level menus are
visible in the main
menu.
3 = Favourites. Only
the favourites and user
level menus are visible
in the main menu.
4 = Monitoring &
Favourites. Monitoring,
favourites and user
level menus are visible
in the main menu.
P8.2 Access Code 0 99999 0 2362
If you set the value to
be to other than 0
before you go to Moni-
toring from, for exam-
ple, Normal, you have
to give the access code
when you go back to
Normal. This prevents
personnel who are not
approved from making
changes in the param-
eters on the control
panel.
CAUTION!
Do not lose the access code. If the access code is lost, contact your nearest service
center or partner.
CHANGING THE ACCESS CODE OF THE USER LEVELS
1 Go to the User levels.
USER SETTINGS, FAVOURITES AND USER LEVEL MENUS VACON · 201
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
8

Table of Contents

Other manuals for Vacon 100 flow

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 100 flow and is the answer not in the manual?

Vacon 100 flow Specifications

General IconGeneral
Protection classIP20
Communication interfaceRS-485
Operating temperature-10°C to +50°C
Storage temperature-40°C to +70°C
Ambient temperature-10°C to +40°C
Control methodSensorless vector control
Communication protocolsCANopen
ApprovalsCE, UL
I/O2 analog inputs
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature
Frequency range0 Hz to 400 Hz
Humidity5% to 95%, non-condensing
Voltage range208-240 V

Related product manuals