EasyManuals Logo

Vacon 100 flow Applications Manual

Vacon 100 flow
386 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #88 background imageLoading...
Page #88 background image
34 Set a value for P3.15.9 Autochange Days Range: Monday to Sunday
35 Set a value for P3.15.10 Autochange Time of Day Range: 00:00:00 to 23:59:59
36 Set a value for P3.15.13 Bandwidth Range: 0-100%
37
Set a value for P3.15.14 Bandwidth Delay
Range: 0-3600 s
The Multi-pump (multidrive) application wizard is completed.
2.6 FIRE MODE WIZARD
To start the Fire mode wizard, make the selection Activate for parameter 1.1.2 in the Quick
setup menu.
CAUTION!
Before you continue, read about the password and warranty in Chapter 10.18 Fire
mode.
1
Set a value for parameter P3.17.2 Fire Mode Fre-
quency Source
More than 1 selection
If you set a value other than Fire mode frequency, the wizard goes directly to step 3.
2
Set a value for parameter P3.17.3 Fire Mode Fre-
quency
Range: varies
3
Activate the signal when the contact opens or when
it closes
0 = Open contact
1 = Closed contact
If you set the value Open contact in step 3, the wizard goes directly to step 5. If you set the
value Closed contact in step 3, step 5 is unnecessary.
VACON · 88 WIZARDS
2
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/

Table of Contents

Other manuals for Vacon 100 flow

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 100 flow and is the answer not in the manual?

Vacon 100 flow Specifications

General IconGeneral
Protection classIP20
Communication interfaceRS-485
Operating temperature-10°C to +50°C
Storage temperature-40°C to +70°C
Ambient temperature-10°C to +40°C
Control methodSensorless vector control
Communication protocolsCANopen
ApprovalsCE, UL
I/O2 analog inputs
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature
Frequency range0 Hz to 400 Hz
Humidity5% to 95%, non-condensing
Voltage range208-240 V

Related product manuals