P3.6.8 FB DATAOUT 8 SELECTION (ID 859)
Use this parameter to select the data that is sent to the fieldbus with the ID number of the
parameter or monitor value.
The data is scaled to an unsigned 16-bit format according to the format on the control panel.
For example, value 25.5 on the display equals 255.
10.8 PROHIBIT FREQUENCIES
In some processes it can be necessary to avoid some frequencies because they make
problems of mechanical resonance. With the Prohibit frequencies function, it is possible to
prevent the usage of these frequencies. When the input frequency reference increases, the
internal frequency reference stays at the low limit, until the input frequency reference is
above the high limit.
P3.7.1 PROHIBIT FREQUENCY RANGE 1 LOW LIMIT (ID 509)
Use this parameter to prevent the drive operating on the prohibited frequencies.
In some processes it can be necessary to avoid some frequencies because they cause
mechanical resonance.
P3.7.2 PROHIBIT FREQUENCY RANGE 1 HIGH LIMIT (ID 510)
Use this parameter to prevent the drive operating on the prohibited frequencies.
In some processes it can be necessary to avoid some frequencies because they cause
mechanical resonance.
P3.7.3 PROHIBIT FREQUENCY RANGE 2 LOW LIMIT (ID 511)
Use this parameter to prevent the drive operating on the prohibited frequencies.
In some processes it can be necessary to avoid some frequencies because they cause
mechanical resonance.
P3.7.4 PROHIBIT FREQUENCY RANGE 2 HIGH LIMIT (ID 512)
Use this parameter to prevent the drive operating on the prohibited frequencies.
In some processes it can be necessary to avoid some frequencies because they cause
mechanical resonance.
P3.7.5 PROHIBIT FREQUENCY RANGE 3 LOW LIMIT (ID 513)
Use this parameter to prevent the drive operating on the prohibited frequencies.
In some processes it can be necessary to avoid some frequencies because they cause
mechanical resonance.
P3.7.6 PROHIBIT FREQUENCY RANGE 3 HIGH LIMIT (ID 514)
Use this parameter to prevent the drive operating on the prohibited frequencies.
In some processes it can be necessary to avoid some frequencies because they cause
mechanical resonance.
PARAMETER DESCRIPTIONS VACON · 281
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
10

Table of Contents

Other manuals for Vacon 100 flow

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 100 flow and is the answer not in the manual?

Vacon 100 flow Specifications

General IconGeneral
Protection classIP20
Communication interfaceRS-485
Operating temperature-10°C to +50°C
Storage temperature-40°C to +70°C
Ambient temperature-10°C to +40°C
Control methodSensorless vector control
Communication protocolsCANopen
ApprovalsCE, UL
I/O2 analog inputs
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature
Frequency range0 Hz to 400 Hz
Humidity5% to 95%, non-condensing
Voltage range208-240 V

Related product manuals