Table 99: Jockey pump parameters
Index Parameter Min Max Unit Default ID Description
P3.21.2.1 Jockey Function 0 2 0 1674
0 = Not used
1 = PID sleep
2 = PID sleep (level)
P3.21.2.2 Jockey Start Level Varies Varies Varies 0.00 1675
P3.21.2.3 Jockey Stop Level Varies Varies Varies 0.00 1676
Table 100: Priming pump parameters
Index Parameter Min Max Unit Default ID Description
P3.21.3.1 Priming Function 0 1 0 1677
0 = Disabled
1 = Enabled
P3.21.3.2 Priming Time 0.0 320.00 s 3.0 1678
Table 101: Anti-blocking parameters
Index Parameter Min Max Unit Default ID Description
P3.21.4.1
Anti-blocking Inter-
val
0 96.0 h 0 1696
P3.21.4.2
Anti-blocking run-
time
0 300 s 20 1697
P3.21.4.3
Anti-blocking fre-
quency
P3.3.1.1 P3.3.1.2 Hz 15.0 1504
VACON · 184 PARAMETERS MENU
5
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/

Table of Contents

Other manuals for Vacon 100 flow

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 100 flow and is the answer not in the manual?

Vacon 100 flow Specifications

General IconGeneral
Protection classIP20
Communication interfaceRS-485
Operating temperature-10°C to +50°C
Storage temperature-40°C to +70°C
Ambient temperature-10°C to +40°C
Control methodSensorless vector control
Communication protocolsCANopen
ApprovalsCE, UL
I/O2 analog inputs
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature
Frequency range0 Hz to 400 Hz
Humidity5% to 95%, non-condensing
Voltage range208-240 V