When the contact is OPEN, the start of the motor is disabled.
When the contact is CLOSED, the start of the motor is enabled.
To stop, the drive obeys the value of P3.2.5 Stop Function.
P3.5.1.16 RUN INTERLOCK 1 (ID 1041)
Use this parameter to select the digital input signal that prevents to start the drive.
The drive can be ready but start is not possible when the state of the interlock signal is 'open'
(damper interlock).
P3.5.1.17 RUN INTERLOCK 2 (ID 1042)
Use this parameter to select the digital input signal that prevents to start the drive.
The drive can be ready but start is not possible when the state of the interlock signal is 'open'
(damper interlock).
If an interlock is active, the drive cannot start.
You can use this function to prevent the start of the drive when the damper is closed. If you
activate an interlock during the operation of the drive, the drive stops.
P3.5.1.18 MOTOR PREHEAT ON (ID 1044)
Use this parameter to select the digital input signal that activates Motor Preheat function.
The Motor Preheat function feeds DC-current to the motor when the drive is in the stop state.
P3.5.1.19 RAMP 2 SELECTION (ID 408)
Use this parameter to select the digital input signal that selects the ramp time to be used.
P3.5.1.20 ACC/DEC PROHIBIT (ID 415)
Use this parameter to select the digital input signal that prevents the acceleration and the
deceleration of the drive.
No acceleration or deceleration is possible until the contact is open.
P3.5.1.21 PRESET FREQUENCY SELECTION 0 (ID 419)
Use this parameter to set the digital input signal that selects the preset frequencies.
P3.5.1.22 PRESET FREQUENCY SELECTION 1 (ID 420)
Use this parameter to set the digital input signal that selects the preset frequencies.
P3.5.1.23 PRESET FREQUENCY SELECTION 2 (ID 421)
Use this parameter to set the digital input signal that selects the preset frequencies.
P3.5.1.24 MOTOR POTENTIOMETER UP (ID 418)
Use this parameter to increase the output frequency with a digital input signal.
The motor potentiometer reference INCREASES until the contact is open.
PARAMETER DESCRIPTIONS VACON · 263
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
10

Table of Contents

Other manuals for Vacon 100 flow

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 100 flow and is the answer not in the manual?

Vacon 100 flow Specifications

General IconGeneral
Protection classIP20
Communication interfaceRS-485
Operating temperature-10°C to +50°C
Storage temperature-40°C to +70°C
Ambient temperature-10°C to +40°C
Control methodSensorless vector control
Communication protocolsCANopen
ApprovalsCE, UL
I/O2 analog inputs
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature
Frequency range0 Hz to 400 Hz
Humidity5% to 95%, non-condensing
Voltage range208-240 V

Related product manuals