Input Pressure
Supervision
Fault Level
Input Pressure Alarm
(Digital output signal)
Supervision
Alarm Level
Input Pressure Monitor
PID Setpoint
PID Setpoint
Supervision
Fault Delay
Supervision
Fault Delay
Motor Running
Yes
No
PID Setpoint
Reduction
Fig. 88: The Input pressure supervision function
P3.13.9.1 ENABLE SUPERVISION (ID 1685)
Use this parameter to enable the Input Pressure Supervision function.
Use this function to make sure that there is enough fluid in the inlet of the pump.
P3.13.9.2 SUPERVISION SIGNAL (ID 1686)
Use this parameter to select the source of the input pressure signal.
P3.13.9.3 SUPERVISION UNIT SELECTION (ID 1687)
Use this parameter to select the unit for the input pressure signal.
You can scale the supervision signal (P3.13.9.2) to process units on the panel.
P3.13.9.4 SUPERVISION UNIT DECIMALS (ID 1688)
Use this parameter to set the number of decimals for the input pressure signal unit.
You can scale the supervision signal (P3.13.9.2) to process units on the panel.
P3.13.9.5 SUPERVISION UNIT MINIMUM VALUE (ID 1689)
Use this parameter to set the minimum value of the input pressure signal.
Enter the value in the selected process unit. For example, an analogue signal of 4...20 mA
corresponds to the pressure of 0...10 bar.
P3.13.9.6 SUPERVISION UNIT MAXIMUM VALUE (ID 1690)
Use this parameter to set the maximum value of the input pressure signal.
Enter the value in the selected process unit. For example, an analogue signal of 4...20 mA
corresponds to the pressure of 0...10 bar.
VACON · 316 PARAMETER DESCRIPTIONS
10
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/

Table of Contents

Other manuals for Vacon 100 flow

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 100 flow and is the answer not in the manual?

Vacon 100 flow Specifications

General IconGeneral
Protection classIP20
Communication interfaceRS-485
Operating temperature-10°C to +50°C
Storage temperature-40°C to +70°C
Ambient temperature-10°C to +40°C
Control methodSensorless vector control
Communication protocolsCANopen
ApprovalsCE, UL
I/O2 analog inputs
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature
Frequency range0 Hz to 400 Hz
Humidity5% to 95%, non-condensing
Voltage range208-240 V

Related product manuals