76
When the power is turned from OFF to ON, the default value is 1.
The available range is 1~32,767, otherwise it is equivalent to 1.
#2
To assign the scale of temperature measurement. 0: ℃ ; 1: ℉ ; other values: ℃ . When the power is turned from OFF to
ON, the default value is 0.
#13
#14
Converted temperature value of TC3, with unit as 0.1 ℃ or 0.1 ℉ .
Converted temperature value of TC4, with unit as 0.1 ℃ or 0.1 ℉ .
Converted temperature value of TC5, with unit as 0.1 ℃ or 0.1 ℉ .
Converted temperature value of TC6, with unit as 0.1 ℃ or 0.1 ℉ .
Converted temperature value of TC7, with unit as 0.1 ℃ or 0.1 ℉ .
Converted temperature value of TC8, with unit as 0.1 ℃ or 0.1 ℉ .
#11
#12
Converted temperature value of TC1, with unit as 0.1 ℃ or 0.1 ℉ .
Converted temperature value of TC2, with unit as 0.1 ℃ or 0.1 ℉ .
#30
#31
Identication code: VS-8TC = K206 (can use the FROM instruction to check whether the place is this module or not)
The version number of this module. (the content value XX indicates Ver. X.X)
#29
Status and error ag.
#3
#4
#5
To set the average times of TC3.
To set the average times of TC4.
#6
To set the average times of TC2.
To set the average times of TC1.
BFM No.
#0
Component Description
To assign the thermocouple types for TC1~TC4. When the power is turned from OFF to ON, the default value is H0000.
To assign the thermocouple types of TC5~TC8. When the power is turned from OFF to ON, the default value is H0000.
#7
#8
#15
#16
#17
#18
#9
#10
To set the average times of TC5.
To set the average times of TC6.
To set the average times of TC7.
To set the average times of TC8.
#1
Example: If the BFM #0 of a VS-8TC is set to be H8100, then
TC1 & TC2: K Type thermocouple input;
TC3: J Type thermocouple input; TC4: disabled.
b15 b0
TC2 TC1TC4 TC3
0
1
2
3
4
5
6
J
K R S T E B
7
N
Value of Nibble
Thermocouple Type
If Value of Nibble is not 0~7,
the channel is disabled.
Nibble #4
Nibble #3
Nibble #2 Nibble #1
BFM#0
b15 b0
TC6 TC5TC8 TC7
b0
b1b2
b6 b3
b7 b4
b5b14~b8b15
BFM#1
Nibble #4
Nibble #3
Nibble #2 Nibble #1
BFM #0 & BFM #1 To appoint the types of thermocouples:
BFM #29 Status and Error Flag: (0: normal; 1: error)
TC1 is disconnected or converted value
exceeds the range
TC2 is disconnected or converted value
exceeds the range
TC3 is disconnected or converted value
exceeds the range
TC4 is disconnected or converted value
exceeds the range
TC5 is disconnected or converted value
exceeds the range
TC8 is disconnected or
converted value exceeds the range
TC7 is disconnected or
converted value exceeds the range
TC6 is disconnected or
converted value exceeds the range
2-17-6 Buffer Memory BFM in the VS-8TC Module
Module's external
DC 24V supply is
missing or has a
hardware error