890370_0•en•01.06.2009 We reserve the right to carry out improvements
137
11 Technical data
Control panel Min. Typ. Max. Unit
Supply
Operating voltage (SELV) 20 24 28 V DC
Current consumption 89 97 170 mA
Internal temperature sensor
Measuring range 0 50 °C
Resolution 0.5 °C
Accuracy ±0.5 °C
Internal humidity sensor
Measuring range 0 99 %RH
Resolution 1 %RH
Accuracy ±3.5 %RH
HF receiver
Receive frequency 433.92 MHz
Dimensions
WxHxD 245x160x28 mm
Degree of protection/safety class
Degree of protection of surface-type
mounting
IP 30
Safety class III
Test standards
Product standard:
EMC basic standards:
DIN EN 60730-1: 2002-1
DIN EN 61000-6-2: 2002-8
DIN EN 61000-6-3: 2002-8
DIN EN 50366: 2003-11
DIN EN 300220-3: 2001-03
EN 301489-3: 2001
Conformity
Ambient conditions
Operating temperature 0 20 50 °C
Storage temperature 0 20 50 °C
Rel. humidity
(non-condensing)
10 40 85 %RH
Technical data