EasyManua.ls Logo

WAREMA climatronic - Use of Repeaters and Hubs; Network Cables; Installing the Control Panel

WAREMA climatronic
144 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
890370_0•en•01.06.2009
We reserve the right to carry out improvements
28
WAREMA climatronic
®
Installation Instructions
4.3.3 Use of repeaters and hubs
Note the following rules:
When using 100 actuators or more, one repeater is required per 100 de-
vices.
One repeater is required after every 1200m of line length.
A maximum of 200actuators, 3weather stations and 2humidity/temperature
sensors may be used in one system.
For installation information for repeaters and hubs, please refer to the instruc-
tions included with these devices.
4.3.4 Network cables
Use only high-grade twisted-pair network cables with a characteristic wave
impedance of 120Ω. We recommend:
JY(St)Y2x2x0.8mmø or JY(St)Y4x2x0.8mmø
YCYM2x2x0.8mmø or YCYM4x2x0.8mmø (Siemens)
Unitronic bus line 2x2x0.8mm ø or 4x2x0.8mmø (LAPP)
UV-resistant cables must be used for outdoor installation (e.g. to connect the
weather station). We recommend:
8xAWG26CULblack
4.4 Installing the control
panel
Because of its flat design, the control panel is intended to be surface-mount-
ed. A flush-mounted box behind it is required for the wiring.
Choose an installation height that permits convenient reading of the display
(recommended: bottom edge of the device approx. 1.45 m above the top
surface of the flooring).
When choosing the installation location, also ensure that the left enclosure
edge is sufficiently far from a wall, cabinet, picture or other obstacle to allow
for the convenient insertion and removal of the SD card and USB cable (rec-
ommended: at least 12-15 cm).
NOTE A temperature sensor is integrated in the control panel itself. Therefore, to
prevent erroneous readings, do not install the control panel where a heat
source may influence the measurements (sunlight, radiator, outside wall).
Mount the base plate on a flush-mounted switch box using suitable fasteners.
Align the base plate exactly level with the help of the elongated holes.
Countersink the 4 countersunk screws included with the delivery to allow the
control panel to fully engage.
Installation