B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 411
Parameter List
B
5 Speed Detection 2
Closed: Output speed is greater than or equal to the value in L4-01 with hysteresis determined by L4-02.
210
6 Drive Ready (READY)
Closed: Power up is complete and the drive is ready to accept an Up/Down command.
211
7 DC Bus Undervoltage
Closed: DC bus voltage is below the Uv trip level set in L2-05.
211
8 During Baseblock (N.O.)
Closed: Drive has entered the baseblock state (no output voltage).
211
9 Speed Reference Source
Open: The speed reference is supplied by an external reference (set in b1-01).
Closed: Digital operator supplies the speed reference.
211
A Up/Down Command Source
Open: The Up/Down command is supplied by an external reference (set in b1-02).
Closed: Digital operator supplies the Up/Down command.
211
B Torque Detection 1
Closed: An overtorque or undertorque situation has been detected.
211
EFault
Closed: Fault occurred. (excluding CPF00 and CPF01)
212
F Not used (Through Mode)
Set this value when the terminal is not used or when using the terminal in the pass-through mode.
212
10 Minor Fault
Closed: An alarm has been triggered, or the IGBTs have reached 90% of their expected life span.
212
11 Fault Reset Command Active
Closed: The drive has received a reset command from the multi-function input terminals or from serial network, or the
digital operator’s RESET key has been pressed.
212
12 Timer Output
Closed: Timer output.
212
13 Speed Agree 2
Closed: When drive output frequency equals the speed reference ±L4-04.
212
14 User-set Speed Agree 2
Closed: When the drive output speed is equal to the value in L4-03 ±L4-04.
212
15 Speed Detection 3
Closed: When the drive output speed is less than or equal to the value in L4-03 ±L4-04.
213
16 Speed Detection 4
Closed: When the output speed is greater than or equal to the value in L4-03 ±L4-04.
213
18 Torque Detection 2
Closed: Overtorque or undertorque has been detected.
211
1A During Down Direction
Closed: Drive is running in the down direction.
214
1B During Baseblock 2 (N.C.)
Open: Drive has entered the baseblock state (no output voltage).
214
1C Motor 2 Selection
Open: Motor 1 is selected
Closed: Motor 2 is selected
214
1D During Regeneration
Closed: Motor is operated in regenerative mode.
215
1E Reset Enabled
Closed: An automatic reset is performed
215
1F Motor Overload Alarm (oL1)
Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers this alarm.
215
H2 Multi-Function Digital Output Settings
H2-
Setting
Function Description Page
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
common_
TMonly
All Modes
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
common_
TMonly
All Modes
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
common_
TMonly
CLV
CLV/PM
V/f OLV
common_
TMonly
CLV
CLV/PM
V/f OLV
All Modes
common_
TMonly
common_
TMonly
All Modes
SIEP_C710616_38F_5_0.book 411 ージ 015年11月9日 月曜日 午後3時36分

Table of Contents

Other manuals for YASKAWA L1000A

Related product manuals