9.4 Monitoring Product Life
9.4.1 Items That You Can Monitor
9-15
9
Monitoring
9.4
Monitoring Product Life
9.4.1
Items That You Can Monitor
Monitor Item Description
SERVOPACK Installation Envi-
ronment
The operating status of the SERVOPACK in terms of the installation envi-
ronment is displayed. Implement one or more of the following actions if the
monitor value exceeds 100%.
Lower the surrounding temperature.
Decrease the load.
Servomotor Installation Environ-
ment
The operating status of the SERVOPACK in terms of the installation envi-
ronment is displayed. Implement one or more of the following actions if the
monitor value exceeds 100%.
Lower the surrounding temperature.
Decrease the load.
Built-in Fan Service Life Predic-
tion
The unused status of the SERVOPACK is treated as the 100% value. The
value decreases each time the main circuit power supply is turned ON and
each time the servo is turned OFF. Use a monitor value of 0% as a guideline
for the replacement period. Refer to the following section for part replace-
ment guidelines.
12.1.2 Guidelines for Part Replacement on page 12-2
Capacitor Service Life Predic-
tion
The unused status of the SERVOPACK is treated as the 100% value. The
value decreases each time the main circuit power supply is turned ON and
each time the servo is turned OFF. Use a monitor value of 0% as a guideline
for the replacement period. Refer to the following section for part replace-
ment guidelines.
12.1.2 Guidelines for Part Replacement on page 12-2
Surge Prevention Circuit Ser-
vice Life Prediction
The unused status of the SERVOPACK is treated as the 100% value. The
value decreases each time the main circuit power supply is turned ON and
each time the servo is turned OFF. Use a monitor value of 0% as a guideline
for the replacement period. Refer to the following section for part replace-
ment guidelines.
12.1.2 Guidelines for Part Replacement on page 12-2
Dynamic Brake Circuit Service
Life Prediction
The unused status of the SERVOPACK is treated as the 100% value. The
value decreases each time the main circuit power supply is turned ON and
each time the servo is turned OFF. Use a monitor value of 0% as a guideline
for the replacement period. Refer to the following section for part replace-
ment guidelines.
12.1.2 Guidelines for Part Replacement on page 12-2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA SGD7S series and is the answer not in the manual?

YASKAWA SGD7S series Specifications

General IconGeneral
SeriesSGD7S
SafetySTO (Safe Torque Off)
Humidity90% RH or less (non-condensing)
Control MethodPWM Control
CommunicationEtherCAT, MECHATROLINK-III, MECHATROLINK-II
Output Power0.1 kW to 15 kW
Feedback SystemIncremental encoder, Absolute encoder
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overload, Overheating, Encoder Error
Ambient Temperature0 to 55°C
Storage Temperature-20 to 85°C
Vibration Resistance5.9 m/s²
InstallationPanel mounted
CertificationsCE, UL, cUL