5.1 Manipulating Parameters (Pn)
5.1.5 Initializing Parameter Settings
5
Basic Functions That Require Setting before Operation
5-11
5.1.5
Initializing Parameter Settings
You can return the parameters to their default settings.
This function will not initialize the settings of the parameters that are adjusted for the Fn009,
Fn00A, Fn00B, Fn00C, Fn00D, Fn00E, and Fn00F utility functions.
Preparations
Always check the following before you initialize the parameter settings.
• The parameters must not be write prohibited.
• The servo must be OFF.
Applicable Tools
The following table lists the tools that you can use to initialize the parameter settings and the
applicable tool functions.
Operating Procedure
Use the following procedure to initialize the parameter settings.
1.
Click the Servo Drive Button in the workspace of the Main Window of the Sig-
maWin+.
2.
Select Edit Parameters in the Menu Dialog Box.
The Parameter Editing Dialog Box will be displayed.
3.
Select any parameter of the axis to initialize.
To enable the new settings, turn the power supply to the SERVOPACK OFF and ON again after
you complete the operation.
Tool Function Reference
Panel Operator Fn005
13.4.5 Initialize Parameters (Fn005) on
page 13-16
Digital Operator Fn005
Σ-7-Series Digital Operator Operating
Manual (Manual No.: SIEP S800001
33)
SigmaWin+ Parameters - Edit Parameters
Operating Procedure on page 5-11