EasyManua.ls Logo

YASKAWA T1000A - Page 112

YASKAWA T1000A
517 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.2 b: Application
112 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
Figure 5.2
Figure 5.2 Setting the Frequency Reference as a Current Signal to Terminal A2
DIP switch S1 must first be set for current input.
Switching between Main/Auxiliary Frequency References
The frequency reference input can be switched between the analog terminals A1, A2, and A3 using multi-speed inputs.
Refer to Multi-Step Speed Selection on page 155 for details on using this function.
Setting 2: MEMOBUS/Modbus Communications
This setting requires that the frequency reference is entered via the RS-485/422 serial communications port (control
terminals R+, R-, S+, S-). For instructions, see MEMOBUS/Modbus Communications on page 445.
Setting 3: Option card
This setting requires that the frequency reference is entered via an option board plugged into connector CN5-A on the
drives control board. Consult the manual supplied with the option board for instructions on integrating the drive with the
communication system.
Note: If the frequency reference source is set for an option PCB (b1-01 = 3), but an option board is not installed, an OPE05 Operator
Programming Error will be displayed on the digital operator and the drive will not run.
Setting 4: Pulse Train Input
If b1-01 is set to 4, the frequency reference must be provided by a pulse train signal to terminal RP. Follow the directions
below to make sure the pulse signal is working properly.
Verifying Pulse Train is Working Properly
Make sure that b1-01 is set to 4 and H6-01 is set to 0.
Set the pulse input scaling H6-02 to the pulse train frequency value that equals 100% of the frequency reference.
Enter a pulse train signal to terminal RP and check if the correct frequency reference is displayed.
n
b1-02: Run Command Source 1
Parameter b1-02 determines the Run command source 1 in the REMOTE mode.
Setting 0: Operator
When the b1-02 = 0, the LO/RE light will switch on and the RUN key will enter a Run command to start the drive.
Setting 1: Control Circuit Terminal
This setting requires that the Run and Stop commands are entered from the digital input terminals. The following
sequences can be used:
2-wire sequence 1:
Two inputs (FWD/Stop-REV/Stop). Initializing the drive by setting A1-03 = 2220, presets the terminals S1 and S2 to
these functions. This is the default setting of the drive. Also refer to Setting 40, 41: Forward run, Reverse run
command for 2-wire sequence on page 187.
2-wire sequence 2:
Two inputs (Start/Stop-FWD/REV). Also refer to Setting 42, 43: Run and direction command for 2-wire sequence 2
No. Parameter Name Setting Range Default
b1-02 Run Command Source 1 0 to 3 1
Drive
A1 Analog Input 1
0 or 4 to 20 mA
AC Analog input common
+V
-V
10.5 V, 20 mA power supply
-10.5 V, 20 mA power supply
A2 Analog Input 2
A3 Analog Input 3
DIP switch S1
VI

Table of Contents

Related product manuals