EasyManua.ls Logo

YASKAWA T1000A - Installing Input Fuses

YASKAWA T1000A
517 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8.5 Installing Peripheral Devices
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual 349
Peripheral Devices &
Options
8
u Installing Input Fuses
NOTICE: When a fuse blows or if drive power has been interrupted, wait briefly before switching the power back on or operating the
peripheral devices.
Check the wiring and the selection of peripheral devices to identify the cause. Contact your supplier before restarting the drive or the
peripheral devices if the cause cannot be identified.
Yaskawa recommends installing a fuse to the input side of the drive to prevent damage to the drive if a short circuit
occurs.
Select the appropriate fuse from the table Table 8.3.
Table 8.3 Input Fuses
Model
CIMR-T
Fuse Type
Manufacturer: Bussmann
Model Fuse Ampere Rating
Three-Phase 200 V Class
2A0004 FWH-70B 70
2A0006 FWH-70B 70
2A0010 FWH-70B 70
2A0012 FWH-70B 70
2A0021 FWH-90B 90
2A0030 FWH-100B 100
2A0040 FWH-200B 200
2A0056 FWH-200B 200
2A0069 FWH-200B 200
2A0081 FWH-300A 300
2A0110 FWH-300A 300
2A0138 FWH-350A 350
2A0169 FWH-400A 400
2A0211 FWH-400A 400
2A0250 FWH-600A 600
2A0312 FWH-700A 700
2A0360 FWH-800A 800
2A0415 FWH-1000A 1000
Three-Phase 400 V Class
4A0002 FWH-40B 40
4A0004 FWH-50B 50
4A0005 FWH-70B 70
4A0007 FWH-70B 70
4A0009 FWH-90B 90
4A0011 FWH-90B 90
4A0018 FWH-80B 80
4A0023 FWH-100B 100
4A0031 FWH-125B 125
4A0038 FWH-200B 200
4A0044 FWH-250A 250
4A0058 FWH-250A 250
4A0072 FWH-250A 250
4A0088 FWH-250A 250
4A0103 FWH-250A 250
4A0139 FWH-350A 350
4A0165 FWH-400A 400
4A0208 FWH-500A 500
4A0250 FWH-600A 600
4A0296 FWH-700A 700
4A0362 FWH-800A 800