5.4 d: Reference Settings
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual 163
Parameter Details
5
u d7: Offset Frequency
n d7-01 to d7-03: Offset Frequency 1 to 3
Three different offset values can be added to the frequency reference. The value is set as a percentage of the maximum
output frequency. They can be selected using digital inputs programmed for Offset frequency 1, 2, and 3 (H1- = 44,
45, 46). The selected offset values are added together if multiple inputs are closed at the same time.
Note: This function can be used to replace the “Trim Control” function (H1- = 1C, 1D) of earlier Yaskawa drives.
Figure 5.43 illustrates the Offset frequency function.
Figure 5.43
Figure 5.43 Offset Frequency Operation
No. Parameter Name Setting Range Default
d7-01 Offset Frequency 1 -100.0 to 100.0% 0%
d7-02 Offset Frequency 2 -100.0 to 100.0% 0%
d7-03 Offset Frequency 3 -100.0 to 100.0% 0%
Frequency
reference
Offset Frequency 1 [d7-01]
(Signed)
Offset Frequency 2 [d7-02]
(Signed)
Offset Frequency 3 [d7-03]
(Signed)
Multi-function
input (44) = on
Multi-function
input (45) = on
Multi-function
input (46) = on
SFS
Frequency
reference after
soft starter

Table of Contents