B.5 Parameter Defaults Determined by Drive Model (o2-04) and Duty Rating (C6-01)
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual 425
Parameter List
B
B.5
Parameter Defaults Determined by Drive Model (o2-04) and Duty Rating (C6-01)
The following tables show parameters and default settings that change with the drive model selection (o2-04). Parameter
numbers shown in parenthesis are valid for motor 2.
Table B.5 200 V Class Drives Default Settings by Drive Model Selection and ND/HD settings
No. Name Unit Default Settings
Model CIMR-T 2A0004 2A0006 2A0010
C6-01 Drive Duty Selection HD ND HD ND HD ND
o2-04 Drive Model Selection Hex. 62 63 65
E2-11 (E4-11) Motor Rated Output kW 0.4 0.75 0.75 1.1 1.5 2.2
b3-04 V/f Gain during Speed Search % 100 100 100 100 100 100
b3-06 Output Current 1 during Speed Search 1 1 0.5 0.5 0.5 0.5
b8-03 Energy Saving Control Filter Time Constant s 0.50 0.50 0.50 0.50 0.50 0.50
b8-04 Energy Saving Coefficient Value 288.2 223.7 223.7 196.6 169.4 156.8
C5-17 (C5-37) Motor Inertia
kgm
2
0.0015 0.0028 0.0028 0.0068 0.0068 0.0088
C6-02Carrier Frequency Selection 111111
E2-01 (E4-01) Motor Rated Current A 1.9 3.3 3.3 4.9 6.2 8.5
E2-02 (E4-02) Motor Rated Slip Hz 2.9 2.5 2.5 2.6 2.6 2.9
E2-03 (E4-03) Motor No-Load Current A 1.2 1.8 1.8 2.3 2.8 3
E2-05 (E4-05) Motor Line-to-Line Resistance Ω 9.842 5.156 5.156 3.577 1.997 1.601
E2-06 (E4-06) Motor Leakage Inductance % 18.2 13.8 13.8 18.5 18.5 18.4
E2-10 (E4-10) Motor Iron Loss for Torque Compensation W 14 26 26 38 53 77
E5-01 Motor Code Selection Hex. 1202 1202 1203 1203 1205 1205
L2-02 Momentary Power Loss Ride-Thru Time s 0.1 0.1 0.2 0.2 0.3 0.3
L2-03 Momentary Power Loss Minimum Baseblock Time s 0.2 0.3 0.3 0.4 0.4 0.5
L2-04 Momentary Power Loss Voltage Recovery Time s 0.3 0.3 0.3 0.3 0.3 0.3
L8-02 Overheat Alarm Level °C 115 115 115 115 115 115
L8-35 Installation Method Selection 2 2 2222
L8-38Carrier Frequency Reduction Selection 222222
n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10
n5-02 Motor Acceleration Time s 0.178 0.142 0.142 0.142 0.166 0.145
n9-12 On-Delay Compensation Time μs 1.8 1.8 1.8 1.8 1.8 1.8
S6-01 DC Bus Capacity μF 500 500 500 500 1000 1000
S6-02 Motor Acceleration Time s 0.178 0.142 0.142 0.142 0.166 0.145