B.5 Parameter Defaults Determined by Drive Model (o2-04) and Duty Rating (C6-01)
426 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
No. Name Unit Default Settings
– Model CIMR-T – 2A0012 2A0021 2A0030
C6-01 Drive Duty Selection – HD ND HD ND HD ND
o2-04 Drive Model Selection Hex. 66 68 6A
E2-11 (E4-11) Motor Rated Output kW 2.2 3.0 3.7 5.5 5.5 7.5
b3-04 V/f Gain during Speed Search % 100 100 100 100 100 100
b3-06 Output Current 1 during Speed Search – 0.5 0.5 0.5 0.5 0.5 0.5
b8-03 Energy Saving Control Filter Time Constant s 0.50 0.50 0.50 0.50 0.50 0.50
b8-04 Energy Saving Coefficient Value – 156.8 136.4 122.9 94.75 94.75 72.69
C5-17 (C5-37) Motor Inertia
kgm
2
0.0088 0.0158 0.0158 0.0255 0.026 0.037
C6-02 Carrier Frequency Selection – 1 1 1 1 1 1
E2-01 (E4-01) Motor Rated Current A 8.5 11.4 14 19.6 19.6 26.6
E2-02 (E4-02) Motor Rated Slip Hz 2.9 2.7 2.73 1.5 1.5 1.3
E2-03 (E4-03) Motor No-Load Current A 3 3.7 4.5 5.1 5.1 8
E2-05 (E4-05) Motor Line-to-Line Resistance Ω 1.601 1.034 0.771 0.399 0.399 0.288
E2-06 (E4-06) Motor Leakage Inductance % 18.4 19 19.6 18.2 18.2 15.5
E2-10 (E4-10) Motor Iron Loss for Torque Compensation W 77 91 112 172 172 262
E5-01 Motor Code Selection Hex. 1206 1206 1208 1208 120A 120A
L2-02 Momentary Power Loss Ride-Thru Time s 0.5 0.5 1 1 1 1
L2-03 Momentary Power Loss Minimum Baseblock Time s 0.5 0.5 0.6 0.7 0.7 0.8
L2-04 Momentary Power Loss Voltage Recovery Time s 0.3 0.3 0.3 0.3 0.3 0.3
L8-02 Overheat Alarm Level °C 125 125 110 110 120 120
L8-35 Installation Method Selection – 2 2 2 2 2 2
L8-38 Carrier Frequency Reduction Selection – 2 2 2 2 2 2
n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10
n5-02 Motor Acceleration Time s 0.145 0.145 0.154 0.168 0.168 0.175
n9-12 On-Delay Compensation Time μs 1.8 1.8 1.6 1.6 1.5 1.5
S6-01 DC Bus Capacity μF 1000 1000 2100 2100 2220 2220
S6-02 Motor Acceleration Time s 0.145 0.145 0.154 0.168 0.168 0.175
No. Name Unit Default Settings
– Model CIMR-T – 2A0040 2A0056 2A0069 2A0081
C6-01 Drive Duty Selection –
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04 Drive Model Selection Hex. 6B 6D 6E 6F
E2-11 (E4-11) Motor Rated Power kW 7.5 11 11 15 15 18.5 18.5 22
b3-04 V/f Gain during Speed Search % 100 100 100 100 100 100 100 100
b3-06 Output Current 1 during Speed Search – 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b8-03 Energy Saving Control Filter Time Constant s 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
b8-04 Energy Saving Coefficient Value – 72.69 70.44 70.44 63.13 63.13 57.87 57.87 51.79
C5-17 (C5-37) Motor Inertia
kgm
2
0.037 0.053 0.053 0.076 0.076 0.138 0.138 0.165
C6-02 Carrier Frequency Selection – 1 1 1 1 1 1 1 1
E2-01 (E4-01) Motor Rated Current A 26.6 39.7 39.7 53 53 65.8 65.8 77.2
E2-02 (E4-02) Motor Rated Slip Hz 1.3 1.7 1.7 1.6 1.6 1.67 1.67 1.7
E2-03 (E4-03) Motor No-Load Current A 8 11.2 11.2 15.2 15.2 15.7 15.7 18.5
E2-05 (E4-05) Motor Line-to-Line Resistance Ω 0.288 0.23 0.23 0.138 0.138 0.101 0.101 0.079
E2-06 (E4-06) Motor Leakage Inductance % 15.5 19.5 19.5 17.2 17.2 15.7 20.1 19.5
E2-10 (E4-10) Motor Iron Loss for Torque Compensation W 262 245 245 272 272 505 505 538
E5-01 Motor Code Selection Hex. 120B 120B 120D 120D 120E 120E 120F 120F
L2-02 Momentary Power Loss Ride-Thru Time s 1 1 2 2 2 2 2 2
L2-03 Momentary Power Loss Minimum Baseblock Time s 0.8 0.9 0.9 1 1 1 1 1
L2-04 Momentary Power Loss Voltage Recovery Time s 0.3 0.3 0.3 0.6 0.6 0.6 0.6 0.6
L8-02 Overheat Alarm Level °C 125 125 120 120 120 120 125 125
L8-35 Installation Method Selection – 2 2 2 2 2 2 2 2
L8-38 Carrier Frequency Reduction Selection – 2 2 2 2 2 2 2 2
n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10 10 10
n5-02 Motor Acceleration Time s 0.175 0.265 0.265 0.244 0.244 0.317 0.317 0.355
n9-12 On-Delay Compensation Time μs1.51.5222222
S6-01 DC Bus Capacity μF 2670 2670 3600 3600 4980 4980 6000 6000
S6-02 Motor Acceleration Time s 0.175 0.265 0.265 0.244 0.244 0.317 0.317 0.355