B.5 Parameter Defaults Determined by Drive Model (o2-04) and Duty Rating (C6-01)
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual 427
Parameter List
B
No. Name Unit Default Settings
– Model CIMR-T – 2A0110 2A0138 2A0169 2A0211
C6-01 Drive Duty Selection –
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04 Drive Model Selection Hex. 70 72 73 74
E2-11 (E4-11) Motor Rated Power kW 22 30 30 37 37 45 45 55
b3-04 V/f Gain during Speed Search % 100 80 80 80 80 80 80 80
b3-06 Output Current 1 during Speed Search – 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b8-03 Energy Saving Control Filter Time Constant s 0.50 0.50 0.50 0.50 0.50 0.50 0.50 2.00
b8-04 Energy Saving Coefficient Value – 51.79 46.27 46.27 38.16 38.16 35.78 35.78 31.35
C5-17 (C5-37) Motor Inertia
kgm
2
0.165 0.220 0.220 0.273 0.273 0.333 0.333 0.490
C6-02 Carrier Frequency Selection – 1 1 1 1 1 1 1 1
E2-01 (E4-01) Motor Rated Current A 77.2 105 105 131 131 160 160 190
E2-02 (E4-02) Motor Rated Slip Hz 1.7 1.8 1.8 1.33 1.33 1.6 1.6 1.43
E2-03 (E4-03) Motor No-Load Current A 18.5 21.9 21.9 38.2 38.2 44 44 45.6
E2-05 (E4-05) Motor Line-to-Line Resistance Ω 0.079 0.064 0.064 0.039 0.039 0.03 0.03 0.022
E2-06 (E4-06) Motor Leakage Inductance % 19.5 20.8 20.8 18.8 18.8 20.2 20.2 20.5
E2-10 (E4-10) Motor Iron Loss for Torque Compensation W 538 699 699 823 823 852 852 960
E5-01 Motor Code Selection Hex. 1210 1210 1212 1212 1213 1213 1214 1214
L2-02 Momentary Power Loss Ride-Thru Time s 2 2 2 2 2 2 2 2
L2-03 Momentary Power Loss Minimum Baseblock Time s 1 1.1 1.1 1.1 1.1 1.2 1.2 1.3
L2-04
Momentary Power Loss Voltage Recovery Ramp
Time
s 0.6 0.6 0.6 0.6 0.6 1 1 1
L8-02 Overheat Alarm Level °C 130 130 130 130 130 130 125 125
L8-35 Installation Method Selection – 0 0 0 0 0 0 0 0
L8-38 Carrier Frequency Reduction Selection –22222222
n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10 10 10
n5-02 Motor Acceleration Time s 0.355 0.323 0.323 0.32 0.32 0.387 0.387 0.317
n9-12 On-Delay Compensation Time μs22222222
S6-01 DC Bus Capacity μF 5800 5800 9400 9400 8000 8000 9600 9600
S6-02 Motor Acceleration Time s 0.355 0.323 0.323 0.32 0.32 0.387 0.387 0.317
No. Name Unit Default Settings
– Model CIMR-T – 2A0250 2A0312 2A0360 2A0415
C6-01 Drive Duty Selection –
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04 Drive Model Selection Hex. 75 76 77 78
E2-11 (E4-11) Motor rated Output kW 55 75 75 90 90 110 110 110
b3-04 V/f Gain during Speed Search % 80 80 80 80 80 80 80 80
b3-06 Output Current 1 during Speed Search – 0.5 0.7 0.7 0.7 0.7 0.7 0.7 0.7
b8-03 Energy Saving Control Filter Time Constant s 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00
b8-04 Energy Saving Coefficient Value – 31.35 23.1 23.1 20.65 20.65 18.12 18.12 18.12
C5-17 (C5-37) Motor Inertia
kgm
2
0.49 0.90 0.90 1.10 1.10 1.90 1.90 1.90
C6-02 Carrier Frequency Selection – 1 1 1 1 1 1 1 1
E2-01 (E4-01) Motor Rated Current A 190 260 260 260 260 260 260 260
E2-02 (E4-02) Motor Rated Slip Hz 1.43 1.39 1.39 1.39 1.39 1.39 1.39 1.39
E2-03 (E4-03) Motor No-Load Current A 45.6 72 72 72 72 72 72 72
E2-05 (E4-05) Motor Line to Line Resistance Ω 0.022 0.023 0.023 0.023 0.023 0.023 0.023 0.023
E2-06 (E4-06) Motor Leakage Inductance % 20.5 20 20 20 20 20 20 20
E2-10 (E4-10) Motor Iron Loss for Torque Compensation W 960 1200 1200 1200 1200 1200 1200 1200
E5-01 Motor Code Selection Hex. 1215 1215 1216 1216 FFFF FFFF FFFF FFFF
L2-02 Momentary Power Loss Ride-Thru Time s 2 2 2 2 2 2 2 2
L2-03 Momentary Power Loss Minimum Baseblock Time s 1.3 1.5 1.5 1.5 1.5 1.7 1.7 1.7
L2-04 Momentary Power Loss Voltage Recovery Times11111111
L8-02 Overheat Alarm Level °C 115 115 120 120 120 120 120 120
L8-35 Installation Method Selection – 0 0 0 0 0 0 0 0
L8-38 Carrier Frequency Reduction Selection –22222222
n1-03 Hunting Prevention Time Constant ms 10 10 10 10 100 100 100 100
n5-02 Motor Acceleration Time s 0.317 0.533 0.533 0.592 0.592 0.646 0.646 0.646
n9-12 On-Delay Compensation Time μs22222222
S6-01 DC Bus Capacity μF 17400 17400 24600 24600 21600 21600 33000 33000
S6-02 Motor Acceleration Time s 0.317 0.533 0.533 0.592 0.592 0.646 0.646 0.646