EasyManua.ls Logo

YASKAWA T1000A - Observing the Drive Operation; Controlling the Drive; Drive Operations by Memobus;Modbus; C.5 Drive Operations by Memobus;Modbus

YASKAWA T1000A
517 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
C.5 Drive Operations by MEMOBUS/Modbus
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual 453
MEMOBUS/Modbus
Communications
C
C.5 Drive Operations by MEMOBUS/Modbus
The drive operations that can be performed by MEMOBUS/Modbus communication depend on drive parameter settings.
This section explains the functions that can be used and related parameter settings.
u Observing the Drive Operation
A PLC can perform the following actions with MEMOBUS/Modbus communications at any time regardless of
parameter settings (except H5-).
Observe drive status and drive control terminal status from a PLC.
Read and write parameters.
Set and reset faults.
Set multi-function inputs. Inputs settings from the input terminals (S1 to S8) and from MEMOBUS/Modbus
communications are both linked by an OR operation.
u Controlling the Drive
To start and stop the drive or set the frequency reference using MEMOBUS/Modbus communications, an external
reference must be selected and the parameters listed in Table C.1 must be adjusted accordingly.
Table C.1 Setting Parameters for Drive Control from MEMOBUS/Modbus
Refer to b1-01: Frequency Reference Source 1 on page 111 and Refer to b1-02: Run Command Source 1 on page 112
for details on external reference parameter selections. Refer to Setting 2: External reference 1/2 selection on page 183
for instructions on how to select external reference 1 and 2.
Reference Source Parameter Name Required Setting
External Reference 1
b1-01 Frequency Reference Source 1 2
b1-02 Run Command Source 1 2
External Reference 2
b1-15 Frequency Reference Source 2 2
b1-16 Run Command Source 2 2

Table of Contents

Related product manuals