164 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
5.5 E: Motor Parameters
5.5 E: Motor Parameters
E parameters cover V/f pattern and motor data settings.
u E1: V/f Pattern for Motor 1
n E1-01: Input Voltage Setting
Set the input voltage parameter to the nominal voltage of the AC power supply. This parameter adjusts the levels of some
protective features of the drive (overvoltage, Stall Prevention, etc.).
NOTICE: Set parameter E1-01 to match the input voltage of the drive. Drive input voltage (not motor voltage) must be set in E1-01 for
the protective features to function properly. Failure to set the correct drive input voltage will result in improper drive operation.
E1-01 Related Values
The input voltage setting when using a 400 V class drive will change the undervoltage detection level for Uv1 and the
KEB function as follows:
Note: The braking transistor operation levels are valid for the drive internal braking transistor. If an external CDBR braking chopper is
used, refer to the instruction manual of that unit.
n V/f Pattern Settings (E1-03)
The drive utilizes a set V/f pattern to determine the appropriate output voltage level for each relative to the frequency
reference.
One custom V/f pattern can be set up by programming parameters E1-04 through E1-13.
n
E1-03: V/f Pattern Selection
This parameter can only be set to F.
n
V/f Pattern Settings E1-04 to E1-13
Using parameters E1-04 through E1-13, the user can either monitor the V/f pattern values if set up a custom V/f pattern
as shown in Figure 5.44 for an example custom V/f pattern.
Note: Certain E1- parameters might not be visible depending on the selected control mode. Refer to Parameter Table on page 367
for details.
No.
<1> The setting range and default value shown here are for 200 V class drives. Double this for 400 V class units.
Parameter Name Setting Range Default
E1-01 <1> Input Voltage Setting 155 to 255 V 200 V
Voltage
Setting Value of
E1-01
(Approximate Values)
Uv Detection Level
(L2-05)
KEB Target Voltage (S4-11)
ov Suppression /
Stall Prevention Level
(L3-17)
200 V Class All settings 190 V 260 V 375 V
400 V Class
setting ≥ 400 V 380 V 500 V 750 V
setting < 400 V 350 V 460 V 750 V
No. Parameter Name Setting Range Default
E1-03 V/f Pattern Selection F F
No. Parameter Name Setting Range Default
E1-04
Maximum Output Frequency
40.0 to 400.0 Hz <1> <2> <3>
E1-05
Maximum Voltage
0.0 to 255.0 V <4> <2> <4>
E1-06
Base Frequency 0.0 to [E1-04]
<2> <3>
E1-07
Middle Output Frequency 0.0 to [E1-04]
<2>
E1-08
Middle Output Frequency Voltage
0.0 to 255.0 V <4> <2> <4>
E1-09
Minimum Output Frequency 0.0 to [E1-04]
<2> <3>
E1-10
Minimum Output Frequency Voltage
0.0 to 255.0 V <4> <2> <4>
E1-11
Middle Output Frequency 2 0.0 to [E1-04]
0.0 Hz <6>
E1-12
Middle Output Frequency Voltage 2
0.0 to 255.0 V <4> 0.0 V <4> <5> <6>
E1-13
Base Voltage
0.0 to 255.0 V <4> 0.0 V <4> <5> <7>