B.3 Parameter Table
398 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
n H6: Pulse Train Input/Output
u L: Protection Function
L parameters provide protection to the drive and motor, such as: control during momentary power loss, Stall Prevention,
frequency detection, fault restarts, overtorque detection, torque limits, and other types of hardware protection.
n
L1: Motor Protection
H5-11
(43CH)
Communications ENTER Function
Selection 0: Drive requires an Enter command before accepting any changes to parameter settings.
1: Parameter changes are activated immediately without the Enter command.
Default: 0
Min: 0
Max: 1
452
H5-12
(43DH)
Run Command Method Selection
0: FWD/Stop, REV/Stop
1: Run/Stop, FWD/REV
Default: 0
Min: 0
Max: 1
452
<20> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
No.(Addr.) Name Description Setting Page
H6-01
(42CH)
Pulse Train Input Terminal RP
Function Selection
0: Frequency reference
1: PID feedback value
2: PID setpoint value
3: V/f Control with Simple PG feedback (possible only when using motor 1 in V/f Control)
Default: 0
Min: 0
Max: 3
209
H6-02
(42DH)
Pulse Train Input Scaling
Sets the terminal RP input signal frequency that is equal to 100% of the value selected in H6-01.
Default: 1440 Hz
Min: 100 Hz
Max: 32000 Hz
210
H6-03
(42EH)
Pulse Train Input Gain
Sets the level of the value selected in H6-01 when a frequency with the value set in H6-02 is
input.
Default: 100.0%
Min: 0.0%
Max: 1000.0%
210
H6-04
(42FH)
Pulse Train Input Bias
Sets the level of the value selected in H6-01 when 0 Hz is input.
Default: 0.0%
Min: -100.0%
Max: 100.0%
210
H6-05
(430H)
Pulse Train Input Filter Time
Sets the pulse train input filter time constant.
Default: 0.10 s
Min: 0.00 s
Max: 2.00 s
210
H6-06
(431H)
Pulse Train Monitor Selection
Select the pulse train monitor output function (value of the - part of U-).
Example: To select U5-01, set “501”.
Note: Set this value as 000 when using the terminal in the pass-through mode.
Default: 102
Min: 000
Max: 502
210
H6-07
(432H)
Pulse Train Monitor Scaling
Sets the terminal MP output signal frequency when the monitor value is 100%. To have the
pulse train monitor output equal the output frequency, set H6-06 to 102 and H6-07 to 0.
Default: 1440 Hz
Min: 0 Hz
Max: 32000 Hz
210
H6-08
(43FH)
Pulse Train Input Minimum
Frequency
Sets the minimum frequency for the pulse train input to be detected. Enabled when H6-01 = 0,
1, or 2.
Default: 0.5 Hz
Min: 0.1 Hz
Max: 1000.0 Hz
210
No. (Addr.) Name Description Setting Page
L1-01
(480H)
Motor Overload Protection
Selection
0: Disabled
1: General purpose motor (standard fan cooled)
2: Drive dedicated motor with a speed range of 1:10
3: Vector motor with a speed range of 1:100
4: PM motor with variable torque
5: PM motor with constant torque control
6: General purpose motor (50 Hz)
The drive may not be able to provide protection when multiple motors are used, even if
overload is enabled in L1-01. Set L1-01 to 0 and install separate thermal relay to each motor.
Default:
<34>
Min: 0
Max: 6
211
L1-02
(481H)
Motor Overload Protection Time
Sets the motor thermal overload protection (oL1) time.
Default: 1.0 min
Min: 0.1 min
Max: 5.0 min
214
L1-03
(482H)
Motor Overheat Alarm Operation
Selection (PTC input)
Sets operation when the motor temperature analog input (H3-02, H3-06, or H3-10 = E) exceeds
the oH3 alarm level.
0: Ramp to stop
1: Coast to stop
2: Fast Stop (decelerate to stop using the deceleration time in C1-09)
3: Alarm only (“oH3” will flash)
Default: 3
Min: 0
Max: 3
216
No.(Addr.) Name Description Setting Page
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes