B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual 397
Parameter List
B
n H5: MEMOBUS/Modbus Serial Communication
H4-02
(41EH)
Multi-Function Analog Output
Terminal FM Gain
Sets the signal level at terminal FM that is equal to 100% of the selected monitor value.
Default: 100.0%
Min: -999.9%
Max: 999.9%
207
H4-03
(41FH)
Multi-Function Analog Output
Terminal FM Bias
Sets the signal level at terminal FM that is equal to 0% of the selected monitor value.
Default: 0.0%
Min: -999.9%
Max: 999.9%
207
H4-04
(420H)
Multi-Function Analog Output
Terminal AM Monitor Selection
Selects the data to be output through multi-function analog output terminal AM.
Set the desired monitor parameter to the digits available in U-. For example, enter “103”
for U1-03.
Default: 103
Min: 000
Max: 999
207
H4-05
(421H)
Multi-Function Analog Output
Terminal AM Gain
Sets the signal level at terminal AM that is equal to 100% of the selected monitor value.
Default: 50.0%
Min: -999.9%
Max: 999.9%
207
H4-06
(422H)
Multi-Function Analog Output
Terminal AM Bias
Sets the signal level at terminal AM that is equal to 0% of the selected monitor value.
Default: 0.0%
Min: -999.9%
Max: 999.9%
207
H4-07
(423H)
Multi-Function Analog Output
Terminal FM Signal Level
Selection
0: 0 to 10 V
1: –10 to 10 V
2: 4 to 20 mA
Default: 0
Min: 0
Max: 2
208
H4-08
(424H)
Multi-Function Analog Output
Terminal AM Signal Level
Selection
0: 0 to 10 V
1: –10 to 10 V
2: 4 to 20 mA
Default: 0
Min: 0
Max: 2
208
No.(Addr.) Name Description Setting Page
H5-01
(425H)
<20>
Drive Node Address
Selects drive station node number (address) for MEMOBUS/Modbus terminals R+, R-, S+, S-.
Cycle power for the setting to take effect.
Default: 1F
Min: 0
Max: FFH
450
H5-02
(426H)
Communication Speed Selection
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Cycle power for the setting to take effect.
Default: 3
Min: 0
Max: 8
450
H5-03
(427H)
Communication Parity Selection
0: No parity
1: Even parity
2: Odd parity
Cycle power for the setting to take effect.
Default: 0
Min: 0
Max: 2
450
H5-04
(428H)
Stopping Method After
Communication Error (CE)
0: Ramp to stop
1: Coast to stop
2: Fast Stop
3: Alarm only
Default: 3
Min: 0
Max: 3
450
H5-05
(429H)
Communication Fault Detection
Selection
0: Disabled
1: Enabled. If communication is lost for more than two seconds, a CE fault will occur.
Default: 1
Min: 0
Max: 1
451
H5-06
(42AH)
Drive Transmit Wait Time
Set the wait time between receiving and sending data.
Default: 5 ms
Min: 5 ms
Max: 65 ms
451
H5-07
(42BH)
RTS Control Selection
0: Disabled. RTS is always on.
1: Enabled. RTS turns on only when sending.
Default: 1
Min: 0
Max: 1
451
H5-09
(435H)
CE Detection Time
Sets the time required to detect a communications error. Adjustment may be needed when
networking several drives.
Default: 2.0 s
Min: 0.0 s
Max: 10.0 s
451
H5-10
(436H)
Unit Selection for MEMOBUS/
Modbus Register 0025H
0: 0.1 V units
1: 1 V units
Default: 0
Min: 0
Max: 1
451
No.(Addr.) Name Description Setting Page
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes