B.3 Parameter Table
368 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
u b: Application
Application parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions,
PID control, the Dwell function, Energy Savings, and a variety of other application-related settings.
n
b1: Operation Mode Selection
No.(Addr.)
<39> The setting range is 0 to 1 in CLV.
Name Description Setting Page
b1-01
(180H)
Frequency Reference Source 1
0: Digital operator
1: Analog input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse input (terminal RP)
Default: 1
Min: 0
Max: 4
111
b1-02
(181H)
Run Command Source 1
0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
Default: 1
Min: 0
Max: 3
112
b1-03
(182H)
Stopping Method Selection
0: Ramp to stop
1: Coast to stop
2: DC Injection Braking to stop
3: Coast with timer
Default: 0
Min: 0
Max: 3
<39>
113
b1-04
(183H)
Reverse Operation Selection
0: Reverse enabled.
1: Reverse disabled.
Default: 0
Min: 0
Max: 1
115
b1-05
(184H)
Action Selection below Minimum
Output Frequency
0: Operates according to frequency reference (E1-09 is disabled).
1: Output shuts off (coast to stop if less than E1-09).
2: Operates according to E1-09 (frequency reference set to E1-09).
3: Zero speed (frequency reference becomes zero when less than E1-09).
Default: 0
Min: 0
Max: 3
115
b1-06
(185H)
Digital Input Reading
0: Input status is read once and processed immediately (for quick response)
1: Input is read twice and processed only if the status is the same in both readings (robust
against noisy signals)
Default: 1
Min: 0
Max: 1
116
b1-07
(186H)
LOCAL/REMOTE Run Selection
0: An external Run command has to be cycled at the new source to be activated.
1: An external Run command at new source is accepted immediately.
Default: 0
Min: 0
Max: 1
117
b1-08
(187H)
Run Command Selection while in
Programming Mode
0: Run command not accepted while in the Programming Mode.
1: Run command accepted while in the Programming Mode.
2: Prohibit entering Programming Mode during run.
Default: 0
Min: 0
Max: 2
117
b1-14
(1C3H)
Phase Order Selection
0: Standard
1: Switch phase order (reverses the direction of the motor)
Default: 0
Min: 0
Max: 1
117
b1-15
(1C4H)
Frequency Reference Source 2
Enabled when an input terminal set for “External reference” (H1- = 2) closes.
0: Digital operator
1: Terminals (analog input terminals)
2: MEMOBUS/Modbus communications
3: Option card
4: Pulse train input
Default: 0
Min: 0
Max: 4
118
b1-16
(1C5H)
Run Command Source 2
Enabled when a terminal set for “External reference” (H1- = 2) closes.
0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option card
Default: 0
Min: 0
Max: 3
118
b1-17
(1C6H)
Run Command at Power Up
0: Disregarded. A new Run command needs to be issued after power up.
1: Allowed. Motor will start immediately after power up if a Run command is already enabled.
Default: 0
Min: 0
Max: 1
118
All Modes
All Modes
All Modes
All Modes
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
All Modes
All Modes
All Modes
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
All Modes
All Modes
All Modes