B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual 371
Parameter List
B
b5-04
(1A8H)
Integral Limit Setting
Sets the maximum output possible from the integrator as a percentage of the maximum output
frequency.
Default: 100.0%
Min: 0.0%
Max: 100.0%
130
b5-05
(1A9H)
Derivative Time (D)
Sets D control derivative time.
Default: 0.00 s
Min: 0.00 s
Max: 10.00 s
130
b5-06
(1AAH)
PID Output Limit
Sets the maximum output possible from the entire PID controller as a percentage of the
maximum output frequency.
Default: 100.0%
Min: 0.0%
Max: 100.0%
131
b5-07
(1ABH)
PID Offset Adjustment
Applies an offset to the PID controller output. Set as a percentage of the maximum output
frequency.
Default: 0.0%
Min: -100.0%
Max: 100.0%
131
b5-08
(1ACH)
PID Primary Delay Time Constant
Sets a low pass filter time constant on the output of the PID controller.
Default: 0.00 s
Min: 0.00 s
Max: 10.00 s
131
b5-09
(1ADH)
PID Output Level Selection
0: Normal output (direct acting)
1: Reverse output (reverse acting)
Default: 0
Min: 0
Max: 1
131
b5-10
(1AEH)
PID Output Gain Setting
Sets the gain applied to the PID output.
Default: 1.00
Min: 0.00
Max: 25.00
131
b5-11
(1AFH)
PID Output Reverse Selection
0: Negative PID output triggers zero limit.
1: Rotation direction reverses with negative PID output.
When using setting 1, make sure reverse operation is permitted by parameter b1-04.
Default: 0
Min: 0
Max: 1
131
b5-12
(1B0H)
PID Feedback Loss Detection
Selection
0: No fault. Digital output only.
1: Fault detection. Alarm output, drive continues operation.
2: Fault detection. Fault output, drive output is shut off.
3: No fault. Digital output only. No fault detection when PID control is disabled.
4: Fault detection. Alarm is triggered and drive continues to run. Fault detection even when PID
is disabled.
5: Fault detection. Drive output shuts off. No fault detection when PID control is disabled.
Default: 0
Min: 0
Max: 5
132
b5-13
(1B1H)
PID Feedback Low Detection
Level
Sets the PID feedback loss detection level as a percentage of the maximum output frequency.
Default: 0%
Min: 0%
Max: 100%
133
b5-14
(1B2H)
PID Feedback Low Detection
Time
Sets a delay time for PID feedback loss.
Default: 1.0 s
Min: 0.0 s
Max: 25.5 s
133
b5-15
(1B3H)
PID Sleep Function Start Level
Sets the frequency level that triggers the sleep function.
Default:
<34>
Min: 0.0 Hz
Max: 400.0 Hz
134
b5-16
(1B4H)
PID Sleep Delay Time
Sets a delay time before the sleep function is triggered.
Default: 0.0 s
Min: 0.0 s
Max: 25.5 s
134
b5-17
(1B5H)
PID Accel/Decel Time
Sets the acceleration and deceleration time to PID setpoint.
Default: 0.0 s
Min: 0.0 s
Max: 6000.0 s
134
b5-18
(1DCH)
PID Setpoint Selection
0: Disabled
1: Enabled
Default: 0
Min: 0
Max: 1
134
b5-19
(1DDH)
PID Setpoint Value
Sets the PID target value when b5-18 = 1. Set as a percentage of the maximum output
frequency.
Default: 0.00%
Min: 0.00%
Max: 100.00%
134
b5-20
(1E2H)
PID Setpoint Scaling
0: 0.01 Hz units
1: 0.01% units (100% = max. output frequency)
2: r/min units (set the no. of motor poles)
3: User-set units (use b5-38, b5-39)
Default: 1
Min: 0
Max: 3
135
b5-34
(19FH)
PID Output Lower Limit
Sets the minimum output possible from the PID controller as a percentage of the maximum
output frequency.
Default: 0.00%
Min: -100.0%
Max: 100.0%
135
No.(Addr.) Name Description Setting Page
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes