B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual 419
Parameter List
B
n U5: PID Monitors
U4-14
(7D0H)
Peak Hold Output Frequency
Displays the output frequency when the current value shown in U4-13 occurred.
No signal output
available
0.01 Hz
U4-16
(7D8H)
Motor Overload Estimate
(oL1)
Shows the value of the motor overload detection accumulator. 100% is equal to the oL1
detection level.
10 V: 100% 0.1%
U4-18
(7DAH)
Frequency Reference Source
Selection
Displays the source for the frequency reference as XY-nn.
X: indicates which reference is used:
1 = Reference 1 (b1-01)
2 = Reference 2 (b1-15)
Y-nn: indicates the reference source
0-01 = Digital operator
1-00 = Analog (not assigned)
1-01 = Analog (terminal A1)
1-02 = Analog (terminal A2)
1-03 = Analog (terminal A3)
2-01 to 2-08, 17 = Multi-step speed (d1-01 to 08, 17)
3-01 = MEMOBUS/Modbus communications
4-01 = Communication option card
5-01 = Pulse input
No signal output
available
––
U4-19
(7DBH)
Frequency Reference from
MEMOBUS/Modbus Comm.
Displays the frequency reference provided by MEMOBUS/Modbus (decimal).
No signal output
available
0.01%
U4-20
(7DCH)
Option Frequency Reference
Displays the frequency reference input by an option card (decimal).
No signal output
available
––
U4-21
(7DDH)
Run Command Source
Selection
Displays the source for the Run command as XY-nn.
X: Indicates which Run source is used:
1 = Reference 1 (b1-02)
2 = Reference 2 (b1-16)
Y: Input power supply data
0 = Digital operator
1 = External terminals
3 = MEMOBUS/Modbus communications
4 = Communication option card
nn: Run command limit status data
00: No limit status.
01: Run command was left on when stopped in the PRG mode
02: Run command was left on when switching from LOCAL to REMOTE operation
03: Waiting for soft charge bypass contactor after power up (Uv or Uv1 flashes after 10 s)
04: Waiting for “Run command prohibited” time period to end
05: Fast Stop (digital input, digital operator)
06: b1-17 (Run command given at power-up)
07: During baseblock while coast to stop with timer
08: Frequency reference is below minimal reference during baseblock
09: Waiting for Enter command
No signal output
available
––
U4-22
(7DEH)
MEMOBUS/Modbus
Communications Reference
Displays the drive control data set by MEMOBUS/Modbus communications register no. 0001H
as a four-digit hexadecimal number.
No signal output
available
––
U4-23
(7DFH)
Communication Option Card
Reference
Displays drive control data set by an option card as a four-digit hexadecimal number.
No signal output
available
––
<49> When reading the value of this monitor via MEMOBUS/Modbus a value of 8192 is equal to 100% of the drive rated output current.
No. (Addr.) Name Description
Analog Output
Level
Unit Page
U5-01
(57H)
PID Feedback
Displays the PID feedback value.
10 V: 100% 0.01%
U5-02
(63H)
PID Input
Displays the amount of PID input (deviation between PID setpoint and feedback).
10 V: 100% 0.01%
U5-03
(64H)
PID Output
Displays PID control output.
10 V: 100% 0.01%
U5-04
(65H)
PID Setpoint
Displays the PID setpoint.
10 V: 100% 0.01%
U5-05
(7D2H)
PID Differential Feedback
Displays the 2nd PID feedback value if differential feedback is used (H3- = 16).
10 V: 100% 0.01%
U5-06
(7D3H)
PID Adjusted Feedback
Displays the difference of both feedback values if differential feedback is used (U5-01 - U5-05).
If differential feedback is not used, then U5-01 and U5-06 will be the same.
10 V: 100% 0.01%
No. (Addr.) Name Description
Analog Output
Level
Unit Page
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes