Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
- / real32
(Visible when 14.1 Module 1 type = FAIO-01)
Displays the value of analog input AI2 after scaling. See
parameter 14.50 AI2 scaled at AI2 min.
This parameter is read-only.
AI2 scaled value14.42
1 = 1 / 1000 = 1Scaled value of analog input AI2.-32768.000 ...
32767.000
- / real32
(Visible when 14.1 Module 1 type = FAIO-01)
Forced value that can be used instead of the true reading
of the input. See parameter 14.22 AI force selection.
AI2 force data14.43
1000 = 1 mA or V /
1000 = 1 mA or V
Forced value of analog input AI2.-22.000 ... 22.000 mA
or V
- / uint16
(Visible when 14.1 Module 1 type = FAIO-01)
Shows the position of the hardware current/voltage selector
on the I/O extension module.
Note: The setting of the current/voltage selector must
match the unit selection made in parameter 14.45 AI2 unit
selection. I/O module reboot either by cycling the power
or through parameter 96.8 Control board boot is required
to validate any changes in the hardware settings.
AI2 HW switch
position
14.44
10Milliamperes.mA
2Volts.V
mA / uint16
(Visible when 14.1 Module 1 type = FAIO-01)
Selects the unit for readings and settings related to analog
input AI2.
Note: This setting must match the corresponding hardware
setting on the I/O extension module (see the manual of the
I/O extension module). The hardware setting is shown by
parameter 14.44 AI2 HW switch position. I/O module reboot
either by cycling the power or through parameter 96.8
Control board boot is required to validate any changes in
the hardware settings.
AI2 unit selection14.45
10Milliamperes.mA
2Volts.V
1 ms / uint16
(Visible when 14.1 Module 1 type = FAIO-01)
Selects a hardware filtering time for AI2.
See also parameter 14.47 AI2 filter time.
AI2 filter gain14.46
0No filtering.No filtering
1125 microseconds.125 us
2250 microseconds.250 us
3500 microseconds.500 us
41 millisecond.1 ms
52 milliseconds.2 ms
64 milliseconds.4 ms
77.9375 milliseconds.7.9375 ms
214 Parameters