Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0 / real32Displays the actual present value of value counter 1.
The value of the source selected by parameter 33.53 Value
counter 1 source is read at one-second intervals and added
to the counter. A divisor can be applied to the count (see
33.54 Value counter 1 divider).
When the counter exceeds the limit set by 33.51 Value
counter 1 warn limit, bit 4 of 33.1 Counter status is set to
1.
The warning specified by 33.55 Value counter 1 warn
message is also given if enabled by 33.52 Value counter
1 function.
The counter can be reset from the Drive Composer PC
tool, or from the control panel by keeping Reset depressed
for over 3 seconds.
Value counter 1
actual
33.50
- / -Actual present value of value counter 1.-2147483000...2147483000
- / real32Sets the limit for value counter 1.
With a positive limit, bit 4 of 33.1 Counter status is set to
1 (and a warning optionally generated) when the counter
is equal or greater than the limit.
With a negative limit, bit 4 of 33.1 Counter status is set to
1 (and a warning optionally generated) when the counter
is equal or smaller than the limit.
0 = Counter disabled.
Value counter 1 warn
limit
33.51
- / -Limit for value counter 1.-2147483000...2147483000
- / uint16Configures value counter 1.Value counter 1
function
33.52
0 = Loop: When the limit is reached, the counter is reset.
The counter status (bit 4 of 33.1) switches to 1 for one
second. The warning (if enabled) stays active for at least
10 seconds.
1 = Saturate: When the limit is reached, the counter status
(bit 4 of 33.1) switches to 1, and remains so until 33.50 is
reset. The warning (if enabled) also stays active until 33.50
is reset.
Counter modeb0
0 = Disable: No warning is given when the limit is reached
1 = Enable: A warning (see 33.55) is given when the limit
is reached
Warning enableb1
Reservedb2…15
1 = 10000h…FFFFh
Not selected / uint32Selects the signal to be monitored by value counter 1.Value counter 1
source
33.53
0None (counter disabled).Not selected
1
1.1 Motor speed used.
Motor speed
See Terms and abbreviations (page 132).
Other [bit]
1.000 / real32Defines a divisor for value counter 1. The value of the
monitored signal is divided by this value before integration.
Value counter 1
divider
33.54
- / -Divisor for value counter 1.0.001 ... 2147483.000
350 Parameters