Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
- / uint16
(Only visible with a BCU control unit)
Specifies the number of inverter modules available.
This parameter must be set if reduced run is required. A
value other than 0 activates the reduced run function.
If the control program cannot detect the number of modules
specified by this parameter, a fault (5695 Reduced run) is
generated.
See section Reduced run function (page 105).
0 = Reduced run disabled
1…12 = Number of modules available
Note: This parameter cannot be changed while the drive
is running.
Reduced run mode95.13
- / -Number of inverter modules available.0...65535
- / uint16
(Only visible with a BCU control unit)
Shows which of the parallel-connected inverter modules
have been detected by the control program.
Note: This parameter is read-only.
Connected modules95.14
Module 1 has been detected.Module 1b0
Module 2 has been detected.Module 2b1
Module 3 has been detected.Module 3b2
Module 4 has been detected.Module 4b3
Module 5 has been detected.Module 5b4
Module 6 has been detected.Module 6b5
Module 7 has been detected.Module 7b6
Module 8 has been detected.Module 8b7
Module 9 has been detected.Module 9b8
Module 10 has been detected.Module 10b9
Module 11 has been detected.Module 11b10
Module 12 has been detected.Module 12b11
Reservedb12…15
1 = 10000h…FFFFh
- / uint16Contains hardware-related settings that can be enabled
and disabled by toggling the specific bits.
Note: The installation of the hardware specified by this
parameter may require derating of drive output, or impose
other limitations. Refer to the hardware manual of the drive.
Note: This parameter cannot be changed while the drive
is running.
Special HW settings95.15
1 = The driven motor is an Ex motor provided by ABB for
potentially explosive atmospheres. This sets the required
minimum switching frequency for ABB Ex motors.
Note: For non-ABB Ex motors, contact your local ABB
representative.
EX motorb0
502 Parameters