FC 300 Design Guide
How to Program
10-31 Store Dat a Values
Option:
*
Off [0]
Store edit setup [1]
Store all setups [2]
Function:
Parameter values changed via DeviceNet are not
automatically stored in non-volatile memory. Use
this p arameter to activate a function that stores
parameter values in the EEPROM non-volatile
memory, so changed parameter values will
be retained at power-down.
Select Off [0] to deactivate the non-volatile
storage function.
Select Store edit setup [1] to store all parameter
values from the act ive set-up in the non-volatile
memory. The selection returns to Off [0] when
all values have been stored.
Select Store all set-ups [2] to store all parameter
values for all set-ups in the non-volatile mem o ry.
The selection returns to Off [0] whe n all parameter
values have been stored.
10-32 Device n et Revision
Range:
0 - 65 535 N/A
*
0N/A
Function:
View the DeviceNet revision number. This
parameter is used for EDS file creation.
10-33 Store Always
Option:
*
Off [0]
On [1]
Function:
Select [0] to deactivate n on-volatile storage of data.
Select [1] to store parameter data received
via Device Net in EEPROM non-volatile
memory as default.
10-39 Devicenet F Parameters
Array [1000]
Option:
No LCP access
0-0
*
0
Function:
This parameter is used to configure the drive
via Dev icenet and build the EDS file.
*
default setting ()display text []value for use in communication via serial communication port
224
MG.33.B
6.22 - V LT is a registered Danfoss trademark