FC 300 Design Guide
How to Program
16-69 Pulse Outp ut #27 [Hz]
Range:
0-0
*
0
Function:
View the actual value of im pulses applied to
terminal 27 in digital output mode.
16-70 Pulse Outp ut #29 [Hz]
Range:
0-0
*
0
Function:
View the actual value of pulses to terminal
29 in digital output mode.
This parameter is available for the FC 302 only.
16-71 Relay Ou tput [bin]
Range:
0-31
*
0
Function:
View the setting s of all relays.
16-72 Counter A
Range:
0-0
*
0
Function:
View the p resent value of Counter A. Counters are
useful as comparator operands, see par. 13-10.
Thevaluecanberesetorchangedeithervia
digital inputs (parameter group 5 -1*) or by
using an SLC action (par. 13-52).
16-73 Counter B
Range:
0-0
*
0
Function:
View the present value of Counter B. Counters are
useful as compa rator operands (par. 1 3-1 0).
The value can be reset or changed either via
digital inputs (parameter group 5-1*) or by
using an SLC action (par. 13-52 ).
16-74 Precise Stop Counter
Range:
-2147483648 - 2147483 648
*
0
Function:
Returns the current counter value of precise
counter (par. 1-84).
" 16-8* Ser. Com. Bus & FC Port
Parameters for reporting the BUS references
and control words.
16-80 Ser. Com. Bus CTW 1
Range:
0 - 65535
*
0
Function:
Viewthetwo-bytecontrolword(CTW)receivedfrom
the bus master. Interpretation of the control word
depends on the serial communication option installed
and the control word pro file selected in p ar. 8-10.
For more information please, refer to the relevant
serial communication bus manual.
16-82 Ser. com. bus REF 1
Function:
Viewthetwo-bytewordsentwiththecontrolword
form the bus master to set the reference value.
For more information please, refer to the relevant
serial communication bus manual.
16-84 Comm. Option STW
Range:
0 - 65535
*
0
Function:
View the extended ser. com. bus option status word.
For more information please, refer to the relevant
serial communication bus manual.
*
default setting ()display text []value for use in communication via serial communication port
249
MG.33.B
6.22 - V LT is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 300 and is the answer not in the manual?

Danfoss FC 300 Specifications

General IconGeneral
BrandDanfoss
ModelFC 300
CategoryDC Drives
LanguageEnglish

Related product manuals