Table 62: Current Ratings for Grid Converter Module, 380–500 VAC (465–800 VDC) (continued)
AC current
(2)(2)
Power, 500 VAC
mains
Frame
Model code
(1)(1)
I
N
[A] I
L
[A] I
H
[A] I
S1
[A] I
S2
[A] P
L
[kW] S
L
[kVA]
Frame
with
option
+AEZ1
or
+AEZ3
(3)(3)
Input
L Filter
size
[A]
(4)(4)
iC7-60SLGCB5-945AE00F4 965 945 708 1418 1323 803 819 2 x
AM12L
2 x
AR12L
1640
iC7-60SLGCB5-1040E00F4 1062 1040 780 1560 1456 883 901 2 x
AM12L
2 x
AR12L
1640
iC7-60SLGCB5-1230E00F4 1256 1230 922 1845 1722 1044 1066 2 x
AM12L
2 x
AR12L
1640
iC7-60SLGCB5-1325E00F4 1353 1325 993 1988 1855 1125 1148 2 x
AM12L
2 x
AR12L
1640
iC7-60SLGCB5-1500E00F4 1532 1500 1125 2250 2100 1274 1300 2 x
AM12L
2 x
AR12L
1640
iC7-60SLGCB5-1700E00F4 1736 1700 1275 2550 2380 1443 1473 3 x
AM12L
3 x
AR12L
2 x 1640
iC7-60SLGCB5-1800E00F4 1838 1800 1350 2700 2520 1528 1559 3 x
AM12L
3 x
AR12L
2 x 1640
iC7-60SLGCB5-2000E00F4 2042 2000 1500 3000 2800 1698 1733 3 x
AM12L
3 x
AR12L
2 x 1640
iC7-60SLGCB5-2250E00F4 2297 2250 1687 3375 3150 1910 1949 3 x
AM12L
3 x
AR12L
2 x 1640
iC7-60SLGCB5-2500E00F4 2552 2500 1875 3750 3500 2122 2166 4 x
AM12L
4 x
AR12L
2 x 1640
iC7-60SLGCB5-2650E00F4 2706 2650 1987 3975 3710 2250 2295 4 x
AM12L
4 x
AR12L
2 x 1640
iC7-60SLGCB5-2940E00F4 3002 2940 2205 4410 4116 2496 2547 4 x
AM12L
4 x
AR12L
2 x 1640
1) The hardware has improved transient withstand.
2) I
S1
and I
S2
are intended for short-circuit current injection in grid forming operation. The rating is valid when the parameter Paralleling sync. Mode is disabled and the maximum
residual voltage of the fault is 30% of nominal at the grid converter terminals. Voltage measurement option OC7V0 is also required.
3) LC Filter +AEZ1, LCL Filter +AEZ3 (grid side L Filter separate module)
4) Part of LCL Filter, +AEZ3
188 | Danfoss Drives Oy © 2024.03 AJ475942178716en-000101 / 172K2848A
Design Guide | iC7 Series Liquid-cooled System Modules