Table 74: Power Loss for INU Modules without Options, Modulator Type 2 (continued)
System
module, 2
kHz switching
frequency
System
module, 3
kHz switching
frequency
System
module, 4
kHz switching
frequency
System
module, 6
kHz switching
frequency
+AKF
X
(1)(1)
Model code Frame Rated
curre
nt
I
L(1/5)
[A]
Power
loss to
liquid
[kW]
Power
loss
to air
[kW]
Power
loss to
liquid
[kW]
Power
loss
to air
[kW]
Power
loss to
liquid
[kW]
Power
loss
to air
[kW]
Power
loss to
liquid
[kW]
Power
loss
to air
[kW]
Power
loss
to air
[kW]
iC7-60SLIN07-1400E
00F_
2xIM12L 1400 9.80 0.10 11.33 0.11 14.37 0.14 - - 0.13
iC7-60SLIN07-1500E
00F_
2xIM12L 1500 10.79 0.11 12.44 0.13 15.84 0.16 - - 0.16
iC7-60SLIN07-1640E
00F_
2xIM12L 1640 12.23 0.12 14.10 0.14 - - - - 0.19
iC7-60SLIN07-1795E
00F_
3xIM12L 1795 11.53 0.12 13.86 0.14 16.92 0.17 21.00 0.21 0.18
iC7-60SLIN07-2080E
00F_
3xIM12L 2080 14.48 0.14 16.79 0.17 21.25 0.21 - - 0.20
iC7-60SLIN07-2300E
00F_
3xIM12L 2300 16.63 0.17 19.24 0.19 - - - - 0.23
iC7-60SLIN07-2500E
00F_
3xIM12L 2500 18.77 0.19 21.64 0.22 - - - - 0.31
iC7-60SLIN07-2830E
00F_
4xIM12L 2830 19.82 0.20 23.00 0.23 29.09 0.29 - - 0.26
iC7-60SLIN07-3050E
00F_
4xIM12L 3050 22.15 0.22 25.47 0.26 - - - - 0.31
iC7-60SLIN07-3260E
00F_
4xIM12L 3260 24.43 0.24 27.95 0.28 - - - - 0.48
iC7-60SLIN07-3500E
00F_
5xIM12L 3500 24.49 0.24 28.33 0.29 35.93 0.36 - - 0.33
iC7-60SLIN07-4035E
00F_
5xIM12L 4035 29.85 0.30 34.45 0.35 - - - - 0.51
iC7-60SLIN07-4400E
00F_
6xIM12L 4400 32.21 0.32 36.21 0.37 47.24 0.47 - - 0.54
iC7-60SLIN07-4850E
00F_
6xIM12L 4850 35.83 0.36 41.45 0.42 - - - - 0.58
iC7-60SLIN07-5300E
00F_
7xIM12L 5300 37.82 0.38 44.14 0.45 55.51 0.56 - - 0.59
iC7-60SLIN07-5600E
00F_
7xIM12L 5600 41.75 0.42 47.64 0.48 - - - - 0.67
206 | Danfoss Drives Oy © 2024.03 AJ475942178716en-000101 / 172K2848A
Design Guide | iC7 Series Liquid-cooled System Modules

Table of Contents

Other manuals for Danfoss iC7 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss iC7 Series and is the answer not in the manual?

Danfoss iC7 Series Specifications

General IconGeneral
Product TypeMedia Converter
Power Supply24 VDC
Housing MaterialPlastic
MountingDIN Rail
ManufacturerDanfoss
Protection ClassIP20
Protocols SupportedModbus
Humidity5% to 95% (non-condensing)
Weight150 g
SeriesiC7 Series

Related product manuals