Chapter 9 Specification
MH300
230V, three-phase
Frame G I
Model VFD_ _ _ _ _ _ _ _ _SAA 75AMH23AN_ _ 90AMH23AN_ _ 120MH23AN_ _ 146MH23AN_ _
Applicable Motor Output (kW) 18.5 22 30 37 (45) *
3
Applicable Motor Output (HP) 25 30 40 50 (60) *
3
*1
Rated Output Capacity (kVA) 28.9 34.4 46.9 57.8
Rated Output Current (A) 75 90 120 146
*2
Rated Output Capacity (kVA) 31.6 37.6 51.3 63.3
Rated Output Current (A) 81 102 134 160
Carrier Frequency (kHz)
*2
2–15 (Default: 4)
Rated Input
Current (A)
Heavy Duty 77 92 117 143
Normal Duty 85 103 126 151
Rated Voltage / Frequency Three-phase, 200–240 V
AC
(-15%– +10%), 50 / 60 Hz
Operating Voltage Range (V
AC
) 170–265
Frequency Range (Hz) 47–63
Weight (kg) 11.8 11.8 33 33.5
Cooling Method Fan cooling
EMC Filter Optional Built-in Optional
Built-in
Optional
Built-in
Optional
Built-in
Ingress Protection Rating
Table 9-4
NOTE:
1. The default is heavy duty mode.
2. The value of the carrier frequency is set in the factory. To increase the carrier frequency, decrease the current.
See the derating curve diagram in Section 9-6.
3. The value in the parentheses is the applicable motor power under normal duty.
4. When the load is a shock or impact load, use a higher level model.