Chapter 11 Summary of Parameter Settings
MH300
11-35
Pr. Parameter Name Setting Range Default
06-49 LvX auto-reset
0: Disable
1: Enable
0
06-53
Treatment for phase loss
protection (OrP)
0: Fault and ramp to stop
1: Fault and coast to stop
0
06-55 Derating protection
0: Constant rated current and limit carrier wave by load
current and temperature
1: Constant carrier frequency and limit load current by
setting carrier wave
2: Constant rated current (same as setting 0), but close
current limit
0
06-56 PT100 voltage level 1 0.00010.000 V 5.000
06-57 PT100 voltage level 2 0.00010.000 V 7.000
06-58
PT100 level 1 frequency
protection
0.00599.00 Hz 0.00
06-59
Delay time for activating
PT100 level 1 frequency
protection
0–6000 sec. 60
06-60
Software detection GFF
current level
0.06553.5% 60.0
06-61
Software detection GFF
filter time
0.00655.35 sec. 0.10
06-63
Operation time of fault
record 1 (Days)
0–65535 days Read only
06-64
Operation time of fault
record 1 (Minutes)
0–1439 min. Read only
06-65
Operation time of fault
record 2 (Days)
0–65535 days Read only
06-66
Operation time of fault
record 2 (Minutes)
0–1439 min. Read only
06-67
Operation time of fault
record 3 (Days)
0–65535 days Read only
06-68
Operation time of fault
record 3 (Minutes)
0–1439 min. Read only
06-69
Operation time of fault
record 4 (Days)
0–65535 days Read only
06-70
Operation time of fault
record 4 (Minutes)
0–1439 min. Read only
06-71 Low current setting level 0.0100.0% 0.0
06-72 Low current detection time 0.00360.00 sec. 0.00