Chapter 11 Summary of Parameter Settings
MH300
11-34
Pr. Parameter Name Setting Range Default
06-29 PTC detection selection
0: Warn and continue operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
0
06-30 PTC level 0.0100.0%
50.0
06-31
Frequency command for
malfunction
0.00599.00 Hz Read only
06-32
Output frequency at
malfunction
0.00599.00 Hz Read only
06-33
Output voltage at
malfunction
0.06553.5 V Read only
06-34 DC voltage at malfunction 0.06553.5 V Read only
06-35
Output current at
malfunction
0.00655.35 Amp Read only
06-36
IGBT temperature at
malfunction
-3276.73276.7ºC Read only
06-38
Motor speed at
malfunction
-3276732767 rpm Read only
06-39
Torque command at
malfunction
-3276732767% Read only
06-40
Status of the multi-function
input terminal at
malfunction
0000hFFFFh Read only
06-41
Status of the multi-function
output terminal at
malfunction
0000hFFFFh Read only
06-42 Drive status at malfunction 0000hFFFFh Read only
06-44 STO latch selection
0: STO Latch
1: STO No Latch
0
06-45
Output phase loss
detection (OPHL) action
0: Warn and continue operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
3
06-46
Detection time of output
phase loss
0.00065.535 sec.
0.500
06-47
Current detection level for
output phase loss
0.00100.00% 1.00
06-48
DC brake time of output
phase loss
0.00065.535 sec.
0.000