Chapter 11 Summary of Parameter Settings
MH300
Pr. Parameter Name Setting Range
Default
10-10 Encoder stall level
0: No function
1–120%
115
10-11
time
0.0–2.0 sec. 0.1
10-12
Encoder stall action
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
2
10-13 Encoder slip range
0: No function
0–50%
50
10-14
Encoder slip detection
time
0.0–10.0 sec. 0.5
10-15
Encoder stall and slip
error action
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
2
10-16 Pulse input type setting
0: Disabled
1: Phases A and B are pulse inputs, forward direction if
A-phase leads B-phase by 90 degrees.
2: Phases A and B are pulse inputs, forward direction if
B-phase leads A-phase by 90 degrees.
3: Phase A is a pulse input and phase B is a direction
input (low input = reverse direction, high input =
forward direction).
4: Phase A is a pulse input and phase B is a direction
input (low input = forward direction, high input =
reverse direction).
5: Single-phase input (MI7)
0
10-17 Electrical gear A 1–65535 100
10-18
Electrical gear B
1–65535
100
10-19
Positioning for encoder
position
-32767
–32767 pulses
0
10-20
Error range for encoder
position reached
0–65535 pulses 10
10-21
Filter time (PG2)
0.000–65.535 sec.
0.100
10-24
FOC & TQC function
control
0–65535 0
10-25
FOC bandwidth for speed
observer
20.0–100.0 Hz 40.0
10-26
FOC minimum stator
frequency
0.0–10.0% fN
2.0