Chapter 11 Summary of Parameter Settings
MH300
Pr. Parameter Name
Setting Range
Default
6: Power factor
7: Power
8: Output torque
9: AVI
10: ACI
12: Iq current command
13: Iq feedback value
14: Id current command
15: Id feedback value
16: Vq-axis voltage command
17: Vd-axis voltage command
18: Torque command
19: PG2 frequency command
20: CANopen analog output
21: RS-485 analog output
22: Communication card analog output
23: Constant voltage output
14-14
AO10 analog output 1 gain
0.0–500.0 % 100.0
14-15 AO11 analog output 1 gain 0.0–500.0 % 100.0
14-16
AVO10 analog output 1 in
REV direction
0: Absolute value of output voltage
1: Reverse output 0 V; forward output 0–10 V
2: Reverse output 5–0 V; forward output 5–10 V
0
14-17
AVO11 analog output 1 in
REV direction
0
14-18
Extension card (AI10)
input selection
0: 0–10 V (AVI10)
1: 0–20 mA (ACI10)
2: 4–20 mA (ACI10)
0
14-19
Extension card (AI11)
input selection
0: 0–10 V (AVI11)
1: 0–20 mA (ACI11)
2: 4–20 mA (ACI11)
0
14-20
AVO10 DC output setting
level
0.00–100.00% 0.00
14-21
AVO11 DC output setting
level
0.00–100.00% 0.00
14-22 AVO10 filter output time 0.00–20.00 sec. 0.01
14-23 AVO11 filter output time 0.00–20.00 sec. 0.01
14-24
AI10 extension card
lowest point
Pr.14-18 = 0: 0.00–10.00 V
Pr.14-18 ≠ 0: 0.00–20.00 mA or 4–20 mA
0.00
14-25
AI10 extension card
proportional lowest point
0.00–100.00% 0.00