Chapter 11 Summary of Parameter Settings
MH300
11-65
Pr. Parameter Name
Setting Range
Default
14-76
Over-torque detection
time (motor 3)
0.060.0 sec. 0.1
14-77
Over-torque detection
action (motor 4)
0: No function
1: Continue operation after over-torque detection during
constant speed operation
2: Stop after over-torque detection during constant speed
operation
3: Continue operation after over-torque detection during
RUN
4: Stop after over-torque detection during RUN
0
14-78
Over-torque detection
level (motor 4)
10250%
(100% corresponds to the rated current of the drive)
120
14-79
Over-torque detection
time (motor 4)
0.060.0 sec. 0.1
14-80
Electronic thermal relay
selection 3 (motor 3)
0: Inverter motor (with external forced cooling)
1: Standard motor (motor with fan on the shaft)
2: Disable
2
14-81
Electronic thermal relay
action time (motor 3)
30.0600.0 sec. 60.0
14-82
Electronic thermal relay
selection 4 (motor 4)
0: Inverter motor (with external forced cooling)
1: Standard motor (motor with fan on the shaft)
2: Disable
2
14-83
Electronic thermal relay
action time (motor 4)
30.0600.0 sec. 60.0