Chapter 12 Descriptions of Parameter Settings
MH300
12.1-00-7
Entering the correct password in Pr.00-07 only temporarily deactivates the password. To
permanently deactivate password protection, set Pr.00-08 to 0 manually. Otherwise, password
protection is always reactivated after you reboot the motor drive.
The keypad copy function works only when the password protection is deactivated (temporarily
or permanently), and the password set in Pr.00-08 cannot be copied to the keypad. So when
copying parameters from the keypad to the motor drive, set the password manually again in the
motor drive to activate password protection.
00-10
Control Mode
Default: 0
Settings
0: Speed mode
1: Position control mode
2: Torque mode
Determines the control mode of the AC motor drive.
00-11
Speed Control Mode
Default: 0
Settings
0: IMVF (IM V/F control)
1: IMVFPG (IM V/F control + Encoder)
2: IM / PM SVC (IM / PM space vector control)
3: IMFOCPG (IM FOC vector control + Encoder)
4: IMFOCPG (PM FOC vector control + Encoder)
5: IMFOC sensorless (IM field-oriented sensorless vector control)
7: IPM sensorless (Interior PM field-oriented sensorless vector control)