Chapter 12 Description of Parameter Settings
MH300
Parallel connection
Feedback Signal Detection Time
Default: 0.0
Settings 0.0–3600.0 sec.
Pr.08-08 is valid only for ACI 4–20 mA.
This parameter sets the detection time for abnormal PID signal feedback. Setting the detection
time to 0.0 disables the detection function.
Feedback Signal Fault Treatment
Default: 0
Settings
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: Warn and operate at last frequency
This parameter is valid only for ACI 4–20 mA.
The AC motor drive acts when the analog PID feedback is abnormal.
Default: 0.00
Settings 0.00–599.00 Hz / 0.00~200.00%
Default: 0.00
Settings 0.00–599.00 Hz / 0.00~200.00%
Determines the sleep frequency, and if the sleep time and the wake-up frequency are enabled
or disabled.
Pr.08-10 = 0: Disabled
Pr.08-10 = ≠ 0: Enabled