EasyManua.ls Logo

Delta MH300 Series - Page 485

Delta MH300 Series
1030 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 12 Description of Parameter Settings
MH300
12.1-08-18
Switch according to the deviation:
When the deviation absolute value between the set point and feedback is smaller than
Pr.08-76 (PID2 Parameter Switch Deviation 1), the first group PID parameters are used.
When the deviation absolute value between the set point and feedback is larger than Pr.08-
77 (PID2 Parameter Switch Deviation 2), the second group PID parameters are used.
When the deviation absolute value between the set point and feedback is between Pr.08-
76 and Pr.08-77, the PID parameter is the linear interpolation value between the two PID
parameter groups.
08-78
Allowed reverse running time after start-up
Default: 0.0
Settings 0.06553.5 sec.
When Pr.08-78 is not set to 0, allowed reverse running time after start-up is enabled.
When it set to 1
second, the PID control is not allowed to change the running direction within 0–
1 seconds of starting time (Pr.08-21 = 0), and is allowed to change after 1 second of starting time
(Pr.08-21 = 1).
08-79
WireBreak detected upper level
Default: 0
Settings 0–100%
08-80
WireBreak detected lower level
Default: 0
Settings 0–100%
08-81
WireBreak detected Time
Default: 0.000
Settings 0.00065.535 sec.
08-82
WireBreak treatment
Default: 0
Settings 0: Warn and do not stop
1: ramp to stop
2: coast to stop
3: Warn, PID hold
Since the tension control may be activated during unwinding, there must be a mechanism to
determine the material cutoff after rewind.

Table of Contents

Related product manuals