Chapter 12 Description of Parameter Settings
MH300
12.1-12-21
12-76
Speed Limit Gain
Default: 0
Settings 0–65535 sec.
In tension mode, when using the analog quantity of linear speed signal as the speed limit (sets
Pr.11-36 = 3), you can use this parameter to adjust the value of the speed limit.
12-77
Tension Control Flag
Default: 0
Settings
bit
0: Tension closed loop speed mode, allowed changing operation direction
bit 1: Start-up compensation (switching between zero-speed tension
command and normal tension command)
bit 2: Acceleration and deceleration compensation (Pr.12-62 Acceleration
inertia compensation gain; Pr.12-
64 Deceleration inertia compensation
gain)
bit 3: Reel diameter calculation by moving average method
bit 5: PID output reverse limit selection
bit 6: Material thickness range selection
Tension related analog input functions
Pr.03-00
Pr.03-01
Setting value Function name
14 Tension PID feedback signal
15 Line speed
16 Reel diameter
17 Tension PID target value
18 Tension setting value
19 Zero-speed tension
20 Tension taper