Chapter 13 Warning Codes|MH300
13-37
ID No.
Display Warning Name Description
44
CANopen SDO
receives register
overflow (CSbn)
CANopen SDO receives register overflow
Action and Reset
Action level
The upper unit sends too much SDO at one time and causes
buffer
overflow
Action time Immediately act when the fault is detected
Warning setting parameter N/A
Reset method The upper unit sends a reset package to clear the warning.
Reset condition N/A
Record N/A
Cause Corrective Actions
Too much SDO from the upper
unit at one time
Check if the master sends too much SDO command. Make sure the
master sends the SDO command according to the command format.