Chapter 13 Warning Codes|MH300
13-38
ID No.
Display Warning Name Description
45
CANopen start-up
error warning (Cbtn)
CANopen start-up error warning
Action and Reset
Action level When the amount of sent error messages reach 255
Action time N/A
Warning setting parameter Index 6007
Reset method Disable CANopen, and cycle the power after power-off
Reset condition N/A
Record N/A
Cause Corrective Actions
Serious interference on
hardware
Verify if the
grounding, terminating resistance and bus line are properly
installed.
Incorrect setting for
communication speed
Verify the setting for communication speed.
The communication card is not
connected, or the card is loose
Make sure the communication card is connected to the drive.