Chapter 14 Fault CodesMH300
ID No.
Display Fault Name Description
10
Over-voltage at stop
(ovS)
Over-voltage at stop
Action and Reset
Action condition
230V series: 410 V
DC
460V series: 820 V
DC
Action time Immediately act when DC bus voltage is higher than the level.
Fault treatment parameter N/A
Reset method Manual reset
Reset condition
Reset only when DC bus voltage is lower than 90% of the over-
level.
Record Yes
Cause Corrective Actions
Power voltage is too high.
Check if the input voltage is
within the rated AC motor drive input voltage
range, and check for possible voltage spikes.
ON/OFF switch action of
phase-in capacitor in the same
power system
If the phase-in capacitor or active power supply unit acts
power system,
the input voltage may surge abnormally in a short time. In
this case, install an AC reactor.
Incorrect wiring of brake
resistor or brake unit
Check the wiring of brake resistor or brake unit.
Malfunction caused by
interference
Verify the wiring of the control circuit and wiring/grounding of the main
circuit to prevent interference.
Hardware failure in voltage
detection
Check if other error codes such as cd1–
cd3 occur after cycling the power.
If yes, return to the factory for repair.
Motor ground fault
The ground
short circuit current charges the capacitor in the main circuit
through the powe
r. Check if there is ground fault on the motor cable,
wiring box and its internal terminals.
Troubleshoot the ground fault.