EasyManua.ls Logo

Delta MH300 Series - Page 742

Delta MH300 Series
1030 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 14 Fault CodesMH300
14-15
ID No.
Display Fault Name Description
11
Low-voltage during
acceleration
(LvA)
DC bus voltage is lower than Pr.06-00
setting value
during acceleration.
Action and Reset
Action condition Pr.06-00 (Default = depending on the model)
Action time Immediately act when DC bus voltage is lower than Pr.06-00.
Fault treatment parameter N/A
Reset method Manual reset
Reset condition Reset when DC bus voltage is higher than Pr.06-00 + 30 V
Record Yes
Cause Corrective Actions
Power-off Improve power supply condition.
Power voltage changes Adjust voltage to the power range of the drive.
Start up the motor with large
capacity.
Check the power system.
Increase the capacity of power equipment.
The load is too large.
Reduce the load.
Increase the drive capacity.
Increase the acceleration time.
DC bus Install DC reactor(s).
Check if there is short circuit
plate or any DC reactor
installed between terminal +1
and +2.
Connect short circuit plate or DC reactor between terminal +1 and +2.
If the error still exists, return to the factory for repair.

Table of Contents

Related product manuals