Chapter 14 Fault CodesMH300
14-67
ID No.
Display Fault Name Description
72
STO Loss 1
(STL1)
S1–DCM internal loop detection error
Action and Reset
Action condition Hardware detection
Action time Immediately act
Fault treatment parameter N/A
Reset method Hardware failure, and cannot reset. Cycle the power.
Reset condition N/A
Record Yes
Cause Corrective Actions
S1 and DCM short circuit lines
are not connected
Re-connect the short circuit line
Hardware failure
After you make sure all the wiring is correct, if STL1
fault still exists after
cycling
the power, return to the factory for repair.