Chapter 16 PLC Function ApplicationsMH300
FOR
Floating point number contact form compare OR*
-
-
-
-
FOR※
Continuous
execution type
-
Flag signal: none
*
*
*
*
*
*
※
:
Refer to the function specifications table for each device in series
for the scope of device usage.
1
: data source device 1. S
2
This command compares the contents of S
1
and S
2
. Taking “FOR=”
example, if the result of comparison is “equal”,
this command activates; but it
does not activate when the result is “unequal”.
The FOR* command can directly input floating point numbers (for instance: F1.2)
to the S
1
and S
2
operands, or store floating point numbers in register D for use in
operations.
You can use this command directly to connect with the busbar.
API No. 32-bit commands
Conditions for
activation
Conditions for
inactivation
287
FOR=
S
1
=S
2
S
1
≠ S
2
288
FOR<
S
1
<S
2
S
1
≤ S
2
289
FOR>
S
1
>S
2
S
1
≥ S
2
290
FOR<>
S
1
≠ S
2
S
1
=S
2
291
FOR=>
S
1
≤ S
2
S
1
<S
2
292
FOR=<
S
1
≥ S
2
S
1
>S
2
When X2 and M30 are both equal to ON, or the floating point number in register
D100 (D101) is greater than or equal to F1.234, then M60=ON.
FOR>= D100 F1.234
X2
M30
M60